TD20 Series VFD
Function
Name
code
Detection level
of the
P11.11
underload
pre-alarm
Detection time
of the
P11.12
underload
pre-alarm
Output
terminal action
P11.13
selection
during fault
Speed
P11.14
deviation
detection
Speed
P11.15
deviation
detection time
Automatic
frequency-d
P11.16
ecreasing at
voltage drop
P13 Group Control parameters of SM
Braking
P13.13
current of
Detailed instruction of parameters
If the VFD current or the output current is lower than
P11.11, and its lasting time is beyond P11.12, the VFD
will output underload pre-alarm.
Setting range of P11.11: 0–P11.09
Setting range of P11.12: 0.1–3600.0s
Select the action of fault output terminals on
undervoltage and fault reset.
0x00–0x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
0.0–50.0%
Set the speed deviation detection time.
This parameter is used to set the speed deviation
detection time.
Speed
Actual detection
value
Set detection
value
t1<t2, so the VFD continues to work
t2=P11.15
Setting range of P11.15: 0.0–10.0s
0: Invalid
1: Valid; ensure rated output torque when voltage drop
After the VFD starts, when P01.00=0, set P13.14 to
non-zero value and begin short circuit braking.
t1
t2
In running
Fault output
-78-
Function Parameters
Default
value
50%
1.0s
0x00
10.0%
0.5s
Time
dEu
0
0.0%
Modify
○
○
○
○
○
○
○