TECHTOP TD20 Series Product Manual page 114

Vfd
Table of Contents

Advertisement

TD20 Series VFD
03E8H. See the table below.
Function
instruction
Communication
control command
The address of
communication
setting
Set P00.01 to 2 and P00.06 to 8.
The command sent to the VFD:
Continuous
VFD
writing
address
command
If the response message is as below:
Example 2: set the ACC time of 01H VFD as 10s and the DEC time as 20s
Function
Name
code
P00.11
ACC time 1
P00.12
DEC time 1
The corresponding address of P00.11 is 000B, the ACC time of 10s corresponds to 0064H, and the DEC
time of 20s corresponds to 00C8H.
The command sent to the VFD:
Address
definition
0001H: forward running
0002H: reverse running
0003H: forward jogging
0004H: reverse jogging
2000H
0005H: stop
0006H: coast to stop (emergency stop)
0007H: fault reset
0008H: jogging stop
Communication setting frequency (0–Fmax
2001H
(unit: 0.01Hz))
PID given, range (0–1000, 1000
2002H
corresponds to100.0%)
Parameters
Data
address
number
Continuous
VFD
writing
address
command
Detailed instruction of parameters
ACC time means the time needed if the VFD speeds up
from 0Hz to the Max. One (P00.03).
DEC time means the time needed if the VFD speeds
down from the Max. Output frequency to 0Hz (P00.03).
TD20 series VFDs have four groups of ACC/DEC time
which can be selected by P05. The factory default
ACC/DEC time of the VFD is the first group.
Setting range of P00.11 and P00.12: 0.0–3600.0s
Data meaning instruction
Byte
number
Parameters
Data
address
number
-112-
Communication Protocol
characteristics
Forward
10Hz
running
CRC check
Default
Depend
Depend
R/W
R/W
R/W
CRC check
Modify
value
on
model
on
model