Device Description - WAGO 750 Manual

16do 24vdc 0.5 a, low-side switching 16-channel digital output module 24 vdc; low-side switching
Table of Contents

Advertisement

WAGO I/O System 750
750-1505 16DO 24VDC 0.5 A, low-side switching
Pos : 17 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 1/Gerätebes chr eibung - Ü berschrift 1 @ 3\mod_1233756084656_21.doc x @ 27096 @ 1 @ 1
3

Device Description

Pos : 18.1 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebesc hrei bung (al te Str uktur)/Ei nleitung/Anwendung/DO/Anwendung 750- x5xx D O @ 3\mod_1233764594468_21.doc x @ 27120 @ @ 1
The 750-1505 (16DO 24VDC 0.5 A, low-side switching) Digital Output Module
transmits binary control signals from the automation device to the connected
actuators (e.g., solenoid valves, contactors, transmitters, relays or other electrical
loads).
Pos : 18.2 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebesc hrei bung (al te Str uktur)/Ei nleitung/I/O-Besc hrei bung/DO/I/O-Besc hrei bung 750-150x 16 D O 1-Leiter CAGE CLAMP @ 3\mod_1233764626734_21.doc x @ 27124 @ @ 1
The I/O module has 16 output channels, providing a direct connection to single-
wire actuators.
The actuators are connected to the CAGE CLAMP
Pos : 18.3 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebesc hrei bung (al te Str uktur)/Ei nleitung/I/O-Besc hrei bung/Allgemein/Ver weis auf Kapi tel " Ansc hlüss e" @ 8\mod_1276775378035_21.doc x @ 57956 @ @ 1
The assignment of the connections is described in the "Connectors" section.
Pos : 18.4 /Dokumentation allgemei n/Glieder ungs elemente/---Leerabs atz-(2Z)--- @ 3\mod_1224662755687_0.doc x @ 24460 @ @ 1
Pos : 18.5 /Serie 750 (WAGO I/O SYSTEM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und sonstige Hinweis e/Hinweis/Hi nweis: D O Potenti al ver vi elfäl tigungs modul e für Aktorvers orgung einsetzen @ 3\mod_1233765481250_21.doc x @ 27140 @ @ 1
Use field side connection modules!
Where required, use the appropriate field side connection modules for power
supply to the actuators.
Pos : 18.6 /Serie 750 (WAGO I/O SYSTEM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und sonstige Hinweis e/Achtung/Ac htung: DO Indukti onss pannungsbegrenzung El ektr oni k @ 3\mod_1233815757507_21.doc x @ 27153 @ @ 1
Limit all induced voltage!
The electronic components of the I/O module can be damaged by the induced
voltage produced when inductive loads are de-activated.
An appropriate protection circuit, e.g., a recovery diode, must be installed in
parallel to the load to limit this induced voltage.
Pos : 18.7 /Serie 750 (WAGO I/O SYSTEM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und sonstige Hinweis e/Achtung/Ac htung: DO Überlastsc hutz - Einpeisekl emme mit Sicherung @ 3\mod_1233814881117_21.doc x @ 27150 @ @ 1
Provide for overload protection!
Overloading can damage the electronic components of the I/O module.
A fused supply module (750-601) must be installed upstream of the I/O module
to protect it against overloading!
Pos : 18.8 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebesc hrei bung (al te Str uktur)/Ei nleitung/I/O-Besc hrei bung/DO/I/O-Besc hrei bung 750- x5xx DO LSS / negati vs chaltend ( 0 V) @ 3\mod_1233817190023_21.doc x @ 27163 @ @ 1
The I/O module outputs provide negative switching. If the signal status of an
output channel is at "high" the 0V potential for field power will be switched to the
appropriate output connection.
Pos : 18.9 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebesc hrei bung (al te Str uktur)/Ei nleitung/LED-Anz eige/LED Zus tand Signal @ 3\mod_1233755258578_21.doc x @ 27087 @ @ 1
A green LED indicates the switched status of each channel.
Pos : 18.10 /Serie 750 ( WAGO I/O SYST EM)/Gerätebeschr eibung (alte Struktur)/Einl eitung/LED- Anzeige/Ver weis auf Kapi tel " Anzeigeel emente" @ 5\mod_1246010525000_21.doc x @ 36194 @ @ 1
The meaning of the LEDs is described in the "Display Elements" section.
Pos : 18.11 /Serie 750 ( WAGO I/O SYST EM)/Gerätebeschr eibung (alte Struktur)/Einl eitung/Vers orgung/Versorg ung 24 V, 0 V über Leistungs kontakte Standard @ 3\mod_1226498974531_21.doc x @ 25020 @ @ 1
The I/O module 750-1505 (16DO 24VDC 0.5 A, low-side switching) receives the
24 V voltage supply for the field level from an upstream I/O module or from the
fieldbus coupler/controller via blade-formed power jumper contacts. It then
provides these potentials to subsequent I/O modules via spring-formed power
jumper contacts.
Pos : 18.12 /Serie 750 ( WAGO I/O SYST EM)/Wichtige Erläuter ung en (alte Struktur)/Sic her hei ts- und s onstige Hi nweise/Ac htung/Ac htung: Maxi maler Str om Leis tungs kontakte 10 A @ 3\mod_1226499143500_21.doc x @ 25029 @ @ 1
connections DO 1 ... DO 16.
®