Parameter Settings; Table 38: Status Byte 0 (Pwm Frq-Cnt); Table 39: Status Byte 2 (Pwm Frq-Cnt) - WAGO 750 XTR Manual

4pwm 24 vdc 0.2a xtr 4 pulse width outputs; 24 vdc; 0.2 a; 20 khz; extreme
Hide thumbs Also See for 750 XTR:
Table of Contents

Advertisement

52
Operating Modes

Table 38: Status Byte 0 (PWM Frq-Cnt)

Bit 7
Reg
General Error
Com
Legend
Enable DO 1 & DO 2
Drivers
PWM enabled
Status of output DO 2
Short circuit DO 1 or
DO 2
Undervoltage
General Error Bit
RegCom

Table 39: Status Byte 2 (PWM Frq-Cnt)

Bit 7
Reg
General Error
Com
Legend
Enable DO 3 & DO 4
Drivers
PWM enabled
Status of output DO 4
Short circuit DO 3 or
DO 4
Undervoltage
General Error Bit
RegCom
Status byte 1 and 3 are permanently "0".
4.3.2

Parameter Settings

The duty cycle can be preset in a range of 0 ... 100 %.
When switching on for the first time, the default value of 50 % is loaded for this
parameter.
Manual
Version 1.0.0
Bit 6
Bit 5
Undervoltage
Bit
0: The status of the output driver for DO 1 & DO 2 is disabled.
1: The status of the output driver for DO 1 and DO 2 is enabled.
0: No output of a PWM signal is enabled.
1: The PWM output is enabled.
0: The output DO 2 is disabled.
1: The output DO 2 is enabled.
0: There is no short circuit at outputs DO 1 or DO 2.
1: There is a short circuit at output DO 1 or DO 2.
0: There is no undervoltage on the I/O module.
1: There is an undervoltage on the I/O module.
0: There is no error.
1: There is an undervoltage or a short circuit.
Bits 0-3 are masked out.
0: Register communication is disabled (normal mode).
1: Register communication is enabled.
Bit 6
Bit 5
Undervoltage
Bit
0: The status of the output driver for DO 3 & DO 4 is disabled.
1: The status of the output driver for DO 3 & DO 4 is enabled.
0: No output of a PWM signal is enabled.
1: The PWM output is enabled.
0: The output DO 4 is disabled.
1: The output DO 4 is enabled.
0: There is no short circuit at outputs DO 3 or DO 4.
1: There is a short circuit at output DO 3 or DO 4.
0: There is no undervoltage on the I/O module.
1: There is an undervoltage on the I/O module.
0: There is no error.
1: There is an undervoltage or a short circuit.
Bits 0-3 are masked out.
0: Register communication is disabled (normal mode).
1: Register communication is enabled.
WAGO I/O System 750 XTR
750-677/040-000 4PWM 24 VDC 0.2A XTR
Status byte 0
Bit 4
Bit 3
Bit 2
Short circuit
Status of
DO 1 or
output
DO 2
DO 2
Status byte 2
Bit 4
Bit 3
Bit 2
Short circuit
Status of
DO 3 or
output
DO 4
DO 4
Bit 1
Bit 0
PWM
Enable DO 1 &
-
enable
DO 2 Drivers
d
Bit 1
Bit 0
PWM
Enable DO 3 &
-
enable
DO 4 Drivers
d

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-677/040-000750-677

Table of Contents