750-677/040-000 4PWM 24 VDC 0.2A XTR
Maximum value of the parameter preset depends on the frequency and duty
cycle
The pulse duration preset is only taken into account up to the value which,
depending on the frequency set, leads to a duty cycle of max. 100 %.
4.4.3

Function of the Output Channels

Output 1 (DO 1): Output signal
Output 2 (DO 2): Count direction
Output 3 (DO 3): Output signal
Output 4 (DO 4): Count direction
*)
L = negative: −1 ... −20,000 Hz or 0xB1E0 to 0xFFFF,
H = positive: 1 ... 20,000 Hz or 0x0001 to 0x4E20
4.4.4

Process Values (Pulse Frq-Cnt)

The frequency is specified in [Hz] via the process output data.
1 digit equals 1 Hz.
Valid value ranges for the process image:
• Positive value range: 0x0001 ... 0x4E20 (1 Hz ... 20000 Hz)
• Negative value range: 0xB1E0 ... 0xFFFF (

Table 46: Process Values (Pulse Frq-Cnt)

Frequency
[Hz]
20000
15000
10000
5000
1
0
1
5000
10000
15000
20000
*)
If the process value = 0, the previous level of the direction output is retained.
*)
*)
Numeric Value
Binary
'0100.1110.0010.0000'
'0011.1010.1001.1000'
'0010.0111.0001.0000'
'0001.0011.1000.1000'
'0000.0000.0000.0001'
'0000.0000.0000.0000'
'1111.1111.1111.1111'
'1110.1100.0111.1000'
'1101.1000.1111.0000'
'1100.0101.0110.1000'
'1011.0001.1110.0000'
Operating Modes
20000 Hz ...
1 Hz)
Hex.
Dec.
0x4E20
20000
0x3A98
15000
0x2710
10000
0x1388
5000
0x0001
1
0x0000
0
0xFFFF
65535
0xEC78
60536
0xD8F0
55536
0xC568
50536
0xB1E0
45536
57
Output
DO 2 or DO 4
High
High
High
High
High
Low oder High
*)
Low
Low
Low
Low
Low