Table 18: Emc - Testing Standards: Immunity To Interference - WAGO 750 XTR Manual

4pwm 24 vdc 0.2a xtr 4 pulse width outputs; 24 vdc; 0.2 a; 20 khz; extreme
Hide thumbs Also See for 750 XTR:
Table of Contents

Advertisement

34
Device Description
Table 18: EMC – Testing Standards: Immunity to Interference
Standard
Electrostatic Discharge
• EN 61000-4-2
• IEEE C37.90.3
High-frequency Electromagnetic Fields
• EN 61000-4-3
• IEEE C37.90.2
Fast Electrical Transient Disturbances / Burst
• EN 61000-4-4
• IEEE C37.90.1
Surge Voltage / Surge
• EN 61000-4-5
Conducted Disturbances, Induced by High-frequency Fields
• EN 61000-4-6
Magnetic Fields With Electrical Frequencies
• EN 61000-4-8
Damped Oscillatory Magnetic Fields
• EN 61000-4-9
Gedämpft schwingende Magnetfelder
• EN 61000-4-10
Voltage Dips, Short-term Interruptions and Voltage Fluctuations
• EN 61000-4-11
Damped Sinusoidal Oscillations
• EN 61000-4-12
Harmonics and Interharmonics
• EN 61000-4-13
Conducted Asymmetric Disturbances
• EN 61000-4-16
Alternating Components of the Voltage to DC Line Connections
• EN 61000-4-17
Damped Oscillatory Waves
• EN IEC 61000-4-18
• IEEE C37.90.1
Voltage Dips, Short-term Interruptions and Voltage Fluctuations to DC Supply
Inputs
• EN 61000-4-29
Manual
Version 1.0.0
WAGO I/O System 750 XTR
750-677/040-000 4PWM 24 VDC 0.2A XTR
Test Value
8 kV (contact discharge)
8 kV (air discharge)
20 V/m (80 MHz ... 1 GHz)
10 V/m (1 GHz ... 6 GHz)
4 kV
1 kV (conductor/conductor)
2 kV (conductor/ground)
10 V (150 kHz ... 80 MHz)
300 A/m continous / 1000 A/m for 1 s
1000 A/m
100 A/m
Standard not applicable
1 kV (conductor/conductor)
2 kV (conductor/ground)
Standard not applicable
To ensure proper function in the event of line
frequency disturbances in accordance with EN
61000-4-16 or EN 60255-26 "Line Frequency
Disturbance Variables" with respect to the
power supply, shielded cables must be used at
cable lengths of 10 m or more.
15 %
1.25 kV conductor/conductor
2.5 kV conductor/ground
Standard not applicable