46
Operating Modes
Output 3 (DO 3): Output signal 3
Output 4 (DO 4): Output signal 4
4.1.4
Process Values
The pulse-pause ratio is specified in [%] via the process output data.
A duty cycle of 100 % corresponds to the value 2048.
Valid value range for the process image: 0 ... 2048
The process value is calculated based on the following formula:
Table 28: Process Values (PWM DC)
Duty cycle [%]
100.00
75.00
50.00
25.00
0.00
Manual
Version 1.0.0
750-677/040-000 4PWM 24 VDC 0.2A XTR
= 2048 ∗
Binary
'0000.1000.0000.0000'
'0000.0110.0000.0000'
'0000.0100.0000.0000'
'0000.0010.0000.0000'
'0000.0000.0000.0000'
WAGO I/O System 750 XTR
[ % ]
100
Numeric Value
Hex.
0x0800
0x0600
0x0400
0x0200
0x0000
Dec.
2048
1536
1024
512
0