9 | Safety function STO

9.6.3 Direct switch-off by safety module with test pulses

S1
S2
open
closed
Acknowledge
Figure 11: Direct switch-off by safety module with test pulses
44
Safety unit
+24V
When the emergency stop device is actuated, e.g. by a safety door, the enable
paths of the safety module are interrupted. This leads to the removal of the STO
signals (X2B.2 and 4) and thus to the energy shutdown of the motor.
The safety module performs a consistency check of all signal paths via test signals
(OSSD).
X4A
Control
Safety
X2B
1 - STO1-
2 - STO1+
3 - STO2-
4 - STO2+
5 - OUT 3
6 - OUT 4
7 - 0V
8 - P24V-IN
Power
U V W PE
X4B
X4C
X2A
X2C
X2D
X1A
ma_dr_f6-cu-k-inst-20144795_en