Power source
Cooling capacity
(Nominal)
Power input
Current input
COP (kW / kW)
Indoor
Temp. range of
Outdoor
cooling
Heating capacity
(Nominal )
Power input
Current input
COP (kW / kW)
Indoor
Temp. range of
heating
Outdoor
Total capacity
Connectable
Model / Quantity
indoor unit
Sound pressure level
(measured in anechoic room)
Liquid (High press.)
Refrigerant piping
diameter
Gas (Low press.)
External finish
External dimension H x W x D
Net weight
Heat exchanger
Compressor
Type
Manufacturer
Starting method
Motor output
Case heater
Lubricant
FAN
Air flow rate
External static press.
Type x Quantity
Control, Driving mechanism
Motor output
HIC circuit
(HIC: Heat Inter-Changer)
Protection
High pressure protection
Inverter circuit (COMP. / FAN)
Compressor
Fan motor
Defrosting method
Refrigerant
Type x Original charge
Control
Drawing
External
Wiring
Refrigerant circle
Standard
Document
attachment
Accessory
Optional parts
Remark
Note :
*1 Nominal cooling conditions
Indoor :
27°CDB/19°CWB (81°FDB/66°FWB)
Outdoor :
35°CDB (95°FDB)
Pipe length :
7.5 m (24-9/16 ft)
Level difference :
0 m (0 ft)
* Nominal conditions *1, *2 are subject to JIS B8615-1.
* Due to continuing improvement, above specifications may be subject to change without notice.
PUMY-P100YHMC-C
kW
*1
kcal / h
*1
BTU / h
*1
kW
A
W.B.
D.B.
10 to 46°CD.B. (50 to 115°FD.B.) : in case of connecting PKFY-P15-P25 type indoor unit.
kW
*2
*2
kcal / h
*2
BTU / h
kW
A
D.B.
W.B.
P15 ~ P125 / 1 ~ 8
dB <A>
mm (in.)
ø9.52 (ø3/8) Flare
mm (in.)
ø15.88 (ø5/8) Flare
mm
1,350 x 950 x 330 (+30)
in.
53-3/16 x 37-7/16 x 13 (+1-3/16)
kg (lbs)
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp.
kW
kW
m
/ min
3
L / s
cfm
Propeller fan x 2
DC-control, Direct-driven by motor
kW
R410A x 8.5kg (19 lbs)
Joint: CMY-Y62-G-E
Header:CMY-Y64/68-G-E
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
*2 Nominal heating conditions
20°CDB (68°FDB)
7°CDB/6°CWB (45°FDB/43°FWB)
7.5 m (24-9/16 ft)
0 m (0 ft)

OUTDOOR UNITS

3-phase 4-wire 380V 50Hz
11.2
9,600
38,200
3.30
5.28
3.39
15 ~ 24°C (59 ~ 75°F)
- 5 ~ 46°C (23 ~ 115°F)
12.5
10,800
42,700
3.63
5.81
3.44
15 ~ 27°C (59 ~ 81°F)
-15 ~ 15°C (5 ~ 59°F)
50 ~ 130% of outdoor unit capacity
49 / 51
Galvanized steel sheet
<MUNSELL 3Y 7.8/1.1>
142 (313)
MITSUBISHI ELECTRIC CORPORATION
Inverter
2.2
-
FV50S
100
1,667
3,531
0 Pa
0.06 x 2
-
High pressure sensor, High pressure switch 4.15 MPa
Over-heat protection, Over-current protection
Compressor thermo protection, Over-current protection
Over-heat protection, Voltage protection
Auto-defrost mode (Reversed refrigerant circle)
LEV circuit
YHM-BK01-B328
YHM-BH79-B325
RC_VBN-050092
Installation Manual
Grounded lead wire x 2
C7-R Rev.
PUMY-P125YHMC-C
14.0
12,000
47,800
4.27
6.83
3.28
16.0
13,800
54,600
4.29
6.87
3.73
P15 ~ P140 / 1 ~ 10
50 / 52
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
1,350 x 950 x 330 (+30)
53-3/16 x 37-7/16 x 13 (+1-3/16)
142 (313)
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp.
2.9
-
FV50S
100
1,667
3,531
0 Pa
Propeller fan x 2
DC-control, Direct-driven by motor
0.06 x 2
R410A x 8.5kg (19 lbs)
Joint: CMY-Y62-G-E
Header:CMY-Y64/68-G-E
Unit converter
kcal/h = kW x 860
BTU/h = kW x 3,412
cfm
= m
3
/min x 35.31
lbs
= kg / 0.4536
*Above specification data is
subject to rounding variation.
2 - 4