Error Code [1301]

1. Error code definition
Low pressure fault
2. Error definition and error detection method
When starting the compressor from Stop Mode for the first time if low pressure reads 0.098MPa [14psi] immediately before
start-up, the operation immediately stops.
3. Cause, check method and remedy
Cause
(1)
Inner pressure drop due to a leakage.
(2)
Low pressure sensor failure
(3)
Short-circuited pressure sensor cable due to
torn outer rubber
(4)
A pin on the male connector is missing.
(5)
Disconnected wire
(6)
Failure of the low pressure input circuit on the
controller board
HWE18240_GB
Check method and remedy
Refer to the following page(s). [8-5-3 Comparing the Low-
Pressure Sensor Measurement and Gauge Pressure]