Technical Data; Electrical Specification - Jetter JetWeb JetMove 203-230 User Manual

Table of Contents

Advertisement

JetMove 203-230
5
5.1
Jetter AG

Technical Data

Electrical Specification

Electrical Specification
Voltage of the rated power supply
Connection type of the voltage
supply
for a rated motor output of >
1kW, a three-phase connection
is compulsory)
Power supply tolerance
Inrush current limitation
Overload protection
Motor output voltage
Motor output current at an ambient
temperature of 45 °C
Continuous power of motor
Short-circuit protection, motor side
Motor overload protection
5.1 Electrical Specification
Direct supply U
= 230 V
eff
Common mode of the voltage 2 % max.
Voltage dips 3 ms max.
48 ... 62 Hz
Frequency change 2 % / s max.
one-phase: direct (U
three-phase: by means of auto- or
isolating transformer
e.g.
in primary circuit:
in secondary circuit: U
See "Note 1!" on page 37.
U
= 195 V ... 265 V (-15 % ... + 15 %)
eff
<45 A limited to 10 ms during the switch-on-
sequence
See "Time between deactivating and
activating the mains power supply" on
page 37
For each phase an external overload
protection is required, for example
– Circuit breaker 4 A C
– Fuse 4 A M (medium time-lag)
– Motor circuit breaker 4 A
Three-phase with 380 V typical (480 V
max.)
Nominal current: I
= 3 A
eff
Peak current for 30 seconds minimum: I
6 A
(The duration depends on the temperature
of the heat sink)
See "Note 2!" on page 37.
0.5 kW
Designed for
phase to phase
phase to earth
See "Motor Protection" on page 39.
= 230V: L to N)
eff
U
= 3 x 400 V.
eff
= 3 x 230 V
eff
=
eff
35