Motor Connection; General Remarks - Jetter JetWeb JetMove 203-230 User Manual

Table of Contents

Advertisement

JetMove 203-230
7.2
7.2.1
Jetter AG

Motor Connection

General remarks

Important!
Alternative measures to avoid malfunctions of the control system and the motor:
Operate the brake via a separately shielded brake line. The distance
between brake line and motor power cable should be greater than 20
cm. This is the preferred solution.
Always connect brake lines to a separate power supply unit DC 24 V if
brake and motor lines are run together in one bunch of cables, and are
not separately shielded.
Important!
Measures to avoid oscillation and blocking of the motor:
Avoid mixing-up of phase cables, resp. be sure to connect the phase
cables according to pin assignment.
7.2 Motor Connection
47

Advertisement

Table of Contents
loading

Table of Contents