3 Operating Conditions
30
EMI Immunity to Interference
Parameters
ESD
RF field
amplitude-modulated
EMI Immunity to Interference
Parameters
Burst (fast transients)
Impulse voltages
Guided radio
disturbances
Operating Parameters
Enclosure
Value(s)
Discharge through air:
Test peak voltage 8 kV
Contact discharge:
Test peak voltage 6 kV
Criterion B
(Second surroundings, restricted
availability)
Frequency band 80 -1000 MHz;
test signal strength 10 V/m
AM 80 % with 1 kHz
Criterion A
(Second surroundings, restricted
availability)
Operating Parameters
Power Connections
Value(s)
Test voltage 2 kV
Repetition rate 5 kHz
Criterion B
(Second surroundings, restricted
availability)
tr/th 1,2/50 µs, 8/20 µs
1 kV (launching phase conductor
against phase conductor)
2 kV (launching phase conductor
against ground potential)
(Second surroundings, restricted
availability)
Frequency 0.15 - 80 MHz
Test voltage 10 V
AM 80 % with 1 kHz
Criterion A
(Second surroundings, restricted
availability)
JetWeb
Standard
Specification(s)
Referred to
DIN EN 61800-3
DIN EN 61000-4-2
DIN EN 61800-3
DIN EN 61000-4-3
Standard
Specification(s)
Referred to
DIN EN 61800-3
DIN EN 61000-4-4
DIN EN 61800-3
DIN EN 61000-4-5
DIN EN 61800-3
DIN EN 61000-4-6