Monitor The Inverter's Variables; List Of Alarms, Warnings And Reasons For Shutdown - Ingeteam INGECON SUN 1Play TL M Installation And Operation Manual

Hide thumbs Also See for INGECON SUN 1Play TL M:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 59
Ingeteam
* This historical meter returns to zero if reset to default settings.

10.18. Monitor the inverter's variables

The monitoring of the inverter variables allows you to see the inverter's operating data in real time.
To view the monitoring, access Main menu > Monitoring and browse through the different screens via the keypads
and
.
The different monitored variables are listed below:
Pac
Inverter AC power, in watts.
Qac
Inverter AC reactive power, in reactive volt-amperes.
Sac
Inverter AC apparent power, in volt-amperes.
CosPhi
Cosine of Phi. Cosine of the phase shift angle between the voltage and current supplied by the
inverter. The cosine of phi can be positive or negative:
Positive: the inverter injects positive reactive energy. The current is ahead with respect to
the voltage.
Negative: the inverter injects negative reactive energy. The current is delayed with respect
to the voltage.
Vac
AC voltage of the inverter, in volts.
Iac
AC current through the inverter, in amperes.
Fac
Frequency generated by the inverter, in hertz.
Pdc
Inverter DC power, in watts.
Pdc1
String 1 DC power, in watts.
Pdc2
String 2 DC power, in watts.
Riso
Insulation resistance of the PV array, in kiloohms.
Vdc1
DC input voltage of string 1.
Vdc2
DC input voltage of string 2.
Idc1
DC input current of string 1.
Idc2
DC input current of string 2.
Total
Energy
Total energy fed through the inverter throughout its useful life.
Time
Total time that the inverter has been feeding the grid.
Connections Total number of grid connections.
Partial
Energy
Partial energy fed by the inverter.
Time
Partial time that the inverter has been connected to the grid.
Connections Partial number of grid connections.
Pac
AC power, in watts
Pwatt
Power fed to the public grid in self consumption mode, in watts.
Ratio
Self consumption ratio. Displays the consumption percentage of the loads being fed by the power
generated by the inverter.

10.19. List of alarms, warnings and reasons for shutdown

During the unit's operation, you can produce alarms, warnings and shutdown reasons.
96
ABE2011IQM01_C - Installation and Operation Manual
Display control

Advertisement

Table of Contents
loading

Table of Contents