List Of The Alarms And Shutdown Reasons - Ingeteam INGECON SUN SMART Installation Manual

Three-phase inverter
Table of Contents

Advertisement

Installation Manual
Ingecon® Sun Three-Phase Inverter
8.2
List of alarms and shutdown reasons
ALARM
0x0000
0x0001
FREC_ALARM
0x0002
VAC_ALARM
0x0004
CURR_PI_SAT_ALARM
0x0008
RESET_ALARM
0x0010
CURRENT_RMS_ALARM
0x0020
TEMPERATURE_ALARM
0x0040
ADC_ALARM
0x0080
CURR.PEAK_ALARM
0x0100
PROT_CA_ALARM
0x0200
PROT_DC_ALARM
0x0400
VARISTORS_ALARM
0x0800
FAULT_ALARM
0x1000
MANUAL_STOP_ALARM
0x2000
CONFIG_ALARM
0x4000
VDC_ALARM
0x8000
MIN_VPV_ALARM
Ref.: AAS2000IKI02
Rev.:_
Dec-2009
The following table shows the reasons that can be in relation with each alarm:
SHUTDOWN REASON
No shutdown
SR_FREC
SR_VAC
SR_CURR_PI_SAT
SR_WD_RESET
SR_CURRENT_RMS
SR_TEMPERATURE
SR_AUX.TEMP
SR_ADC_READING
SR_ADC_LAT
SR_CURR.PEAK
SR_VARISTORS
SR_CONTACTOR
SR_AC_PROT
SR_AC_MAG_PROT
SR_PARO_FUS_DC
SR_VARISTORS
SR_FAULT(1)
SR_FAULT(2)
SR_FAULT(3)
SR_MANUAL_STOP
SR_CONFIG
SR_FIRMWARE.CH
SR_VDC
SR_MIN_VPV
DESCRIPCTION
No alarm, the inverter will start up if it has enough power
Grid Frequency out of range
Grid Voltage out of range
Red current is much more lower than the target current in that phase
Firmware fault.
RMS current value exceeds maximun alowed value
Electronics temperature exceeds 80ºC.
Temperature auxiliar sensor has detected an alarma
Error in Analog-to-Digital Converter
Internal Error of the Analog-to-Digital Converter
Instantaneus current value out of range
Error at AC varistors of AAS0043
Status of contactor incoherent with the status of the inverter.
Error at AC protections, dischargers, fuses...
Error at three-phase input breaker (60 to 100 kW inverters)
DC input fuses fused, or DC dischargers
Error en los varistores de DC
Line 1 power electronics Fault
Line 2 power electronics Fault
Line 3 power electronics Fault
Manual Stop by Emergency Mushroom, display or comunication.
Stop by a Firmware modification
Stop by a Firmware upload
High voltage at DC input.
Stop because of low voltage. As the inverter controls this voltage, it
should never happen.
Pg. 35 de 40