96
Operation
8.2.1.2
Setting an Analog Output
To set an analog output, send an SMS with the text, which is entered under Set
output, and the value to be set to the TO-PASS
PASS® telecontrol module acknowledges the command with an SMS containing
the identifier, the transmitted text and the set value.
Example:
Table 46: Example of parameters for Set AO1
Parameter
Output Signal
Min. value
Max. value
Unit
Text
Send an SMS with the text "AOUT1=75" to set analog output 1 to a value of 15
mA = 75%. The TO-PASS
an SMS containing the identifier and the text "AOUT1=+00075% OK!".
Starting with Firmware 02.33.08, places after the decimal point are also taken into
account for setting of the analog outputs. A period (decimal point) "." must be
used as the separator. Up to four digits are evaluated. For 0 .... 100%, one digit
remains to be used after the decimal point, allowing a value of "75.5" to be
evaluated, for example.
"AOUT1=+075.5%OK!" is transmitted as a reply.
761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485
Setting
0 ... 20 mA
0
100
%
AOUT1=
®
telecontrol module acknowledges the command with
WAGO-TO-PASS® 761
®
telecontrol module. The TO-
Manual
Version 1.0.0