Telecontrol module compact, 2 ai, web, modbus485 for wago-to-pass 761, telecontrol module for fault detection/indication, monitoring and remote control
Telecontrol module compact, 2 ai, web for wago-to-pass 761. telecontrol module for fault detection/indication, monitoring and remote control. (116 pages)
Ttl incremental/ssi encoder 2 encoder interfaces (2 x m12) + 4 digital inputs/outputs (2 x m12, 2 inputs/outputs per connector) for wago-speedway 767 (102 pages)
Summary of Contents for WAGO 761-114
Page 1
Manual WAGO-TO-PASS® 761 Telecontrol Module Compact, 2 AI, Web, MODBUS485 761-114 Telecontrol module for fault detection/indication, monitoring and remote control Version 1.0.0...
WAGO-TO-PASS® 761 Table of Contents 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table of Contents Notes about this Documentation ..............7 Validity of this Documentation ..............7 Copyright ....................7 Symbols ..................... 8 Number Notation ..................10 Font Conventions ..................10 Important Notes ..................
Page 4
Table of Contents WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 3.6.6 Digital Inputs ..................34 3.6.7 Counter Inputs ..................34 3.6.8 Analog Inputs ..................35 3.6.9 Digital Outputs ................... 35 Approvals ....................36 Standards and Guidelines ................ 36 Mounting .....................
Care must also be taken to ensure that any supplement to these instructions are included, if applicable. Validity of this Documentation This documentation is only applicable to the telecontrol module 761-114 (Telecontrol Module Compact, 2 AI, Web, MODBUS485). Copyright This Manual, including all figures and illustrations, is copyright-protected.
Notes about this Documentation WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Symbols Personal Injury! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury. Personal Injury Caused by Electric Current! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury.
Page 9
WAGO-TO-PASS® 761 Notes about this Documentation 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Additional Information: Refers to additional information which is not an integral part of this documentation (e.g., the Internet). Manual Version 1.0.0...
Notes about this Documentation WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Number Notation Table 1: Number notation Number code Example Note Decimal Normal notation Hexadecimal 0x64 C notation Binary '100' In quotation marks, nibble separated with '0110.0100' dots (.)
2.1.1 Subject to Changes WAGO Kontakttechnik GmbH & Co. KG reserves the right to provide for any alterations or modifications that serve to increase the efficiency of technical progress. WAGO Kontakttechnik GmbH & Co. KG owns all rights arising from the granting of patents or from the legal protection of utility patents.
GPL. According to Section 3b of GPL, we offer you the source code. You can obtain the source code with licensing terms of the Open Source software from WAGO Kontakttechnik GmbH & Co. KG on request. Send your request to support@wago.com with the subject "Open Source TO-PASS Compact".
WAGO-TO-PASS® 761 Important Notes 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Safety Advice (Precautions) For installing and operating purposes of the relevant device to your system the following safety precautions shall be observed: Do not work on components while energized! All power sources to the device shall be switched off prior to performing any installation, repair or maintenance work.
Page 14
Important Notes WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Please note the following information about FCC Part 15! FCC Part 15.19 This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: 1.
Page 15
WAGO-TO-PASS® 761 Important Notes 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Protect the components against materials having seeping and insulating properties! The components are not resistant to materials having seeping and insulating properties such as: aerosols, silicones and triglycerides (found in some hand creams).
Please note that one SIM card is required to operate each TO-PASS telecontrol module and may be obtained from typical service providers such as T-Mobile, VODAFONE or EPlus. WAGO Kontakttechnik GmbH & Co. K.G. is prepared to assist with the selection of the most cost-effective tariff for your application. ®...
WAGO-TO-PASS® 761 Device Description 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Connectors 3.4.1 Antenna The screw connector (SMA socket) for the GSM antenna is located at the top of the housing. Figure 2: Antenna connection Observe the maximum length of the antenna cable!
Device Description WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 3.4.2 Operating Voltage Use SELV/PELV power source only! ® The TO-PASS telecontrol module must only be powered from a PELV (Protective Extra Low Voltage) or SELV (Safety Extra Low Voltage) power source complying with the limited power source (LPS) requirements per DIN EN 60950-1.
WAGO-TO-PASS® 761 Device Description 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 3.4.3 Grounding 3.4.3.1 Framework Assembly When setting up the framework, the carrier rail must be screwed together with the electrically conducting cabinet or housing frame. The framework or the housing must be grounded.
Higher shielding performance is achieved via low-impedance connection between shield and ground. To achieve this, connect the shield over a large surface area, e.g., WAGO shield connecting system. This is especially recommended for large- scale systems where equalizing current or high impulse-type currents caused by atmospheric discharge may occur.
3.4.4.4 WAGO Shield Connecting System The WAGO shield connecting system consists of shield clamping saddles, busbars and various mounting carriers to enable a wide variety of setups. For more information on this, refer to the "Accessories" section of the main catalog.
Device Description WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 3.4.5 Digital Inputs Only connect SELV/PELV voltages! Only SELV/PELV voltages shall be connected to the device terminals. Table 6: Terminal assignment for digital inputs Figure 5: Terminal assignment for digital inputs...
WAGO-TO-PASS® 761 Device Description 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 3.4.6 Counter Inputs Only connect SELV/PELV voltages! Only SELV/PELV voltages shall be connected to the device terminals. Digital inputs D1 … D4 can be configured as counter inputs.
Device Description WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 3.4.7 Analog Inputs Only connect SELV/PELV voltages! Only SELV/PELV voltages shall be connected to the device terminals. Table 8: Terminal assignment for analog inputs Figure 7: Terminal assignment for analog inputs...
Page 27
WAGO-TO-PASS® 761 Device Description 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Analog inputs are single-ended! The analog inputs are single-ended and the “Aix–” connections are connected internally to the “GND” connections. Connect shielding! Shielded cables are required for analog inputs. The cable shield must be connected to the grounded DIN rail (see section "Connections"...
Device Description WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 3.4.8 Digital Outputs Only connect SELV/PELV voltages! Only SELV/PELV voltages shall be connected to the device terminals. Table 9: Terminal assignment for digital outputs Figure 8: Terminal assignment for digital outputs...
WAGO-TO-PASS® 761 Device Description 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 3.4.9 Serial Interface to the PC and MODBUS Interface Table 10: Serial interface to the PC and MODBUS interface Description Not assigned Not assigned Not assigned MODBUS D1 (B)
Page 31
WAGO-TO-PASS® 761 Device Description 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Connect shielding! Shielded cables are required for MODBUS communication. The cable shield must be connected to the DIN rail (see section "Connections" > "Shielding"). Manual Version 1.0.0...
Device Description WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Display Elements Table 13: Display Elements Busy Description Green 0.5 Hz Ready to operate blinking Communication via RS232 Green interface Green 1 Hz Firmware update blinking GSM modem is activated Initialization (takes approx.
WAGO-TO-PASS® 761 Device Description 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Technical Data 3.6.1 Housing Table 14: Technical Data Housing Dimensions (W x H x L) 109 mm x 105 mm x 78 mm Weight Approx. 412 g Operating temperature -20 °C ...
WAGO-TO-PASS® 761 Device Description 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 3.6.8 Analog Inputs Table 21: Technical Data Analog Inputs Number of inputs Input current 0/4 mA ... 20 mA Approx.. 200 Ω / 20 mA Internal resistance Resolution 12 bit Measuring error (25°C)
IP20 degree of protection ® The protection class of the TO-PASS telecontrol module is IP 20. For this reason, WAGO Kontakttechnik GmbH & Co. KG recommends mounting in a housing or in a switching cabinet. Ambient temperature -20 °C to +70 °C ®...
Mounting WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 ® Removing the TO-PASS telecontrol module from the DIN rail ® Figure 13: Removing the TO-PASS telecontrol module from the DIN rail ® Press the undersurface against the lower DIN rail edge until the TO-PASS telecontrol module is no longer locked in place.
If more than one conductor must be routed to one connection, these must be connected in an up-circuit wiring assembly, for example using WAGO feed- through terminals. Terminate both solid and ferruled conductors without actuation by simply pushing them in.
Connect Devices WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Connection Examples Connect the shield connection to the DIN rail! ® The shield connection of the TO-PASS telecontrol module (shield, terminal 38) must be connected to the DIN rail. The DIN rail must have a low-impedance ground (see section "Connections"...
WAGO-TO-PASS® 761 Connect Devices 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 5.2.2 Counter Inputs Only connect SELV/PELV voltages! Only SELV/PELV voltages shall be connected to the device terminals. Connect shielding! Shielded cables are recommended for the counter inputs. When using shielded cables, the shield must be routed to the grounded DIN rail (see Section "Connections"...
Connect Devices WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 5.2.3 Analog Inputs Only connect SELV/PELV voltages! Only SELV/PELV voltages shall be connected to the device terminals. Analog inputs are single-ended! The analog inputs are single-ended and the “Aix–” connections are connected internally to the “GND”...
® since the internal resistance of the TO-PASS telecontrol module depends on the input current. WAGO 857 Series JUMPFLEX Isolation Amplifiers for level conversion may be ® used for voltage measurement via TO-PASS telecontrol modules. Figure 17: Connection example for voltage measurement via U/I converter at input AI1 Manual Version 1.0.0...
Connect Devices WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 5.2.4 Digital Outputs Only connect SELV/PELV voltages! Only SELV/PELV voltages shall be connected to the device terminals. Figure 18: Connection example for a relay at DO1 output Manual...
WAGO-TO-PASS® 761 Connect Devices 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 5.2.5 MODBUS Interface MODBUS Line terminator The MODBUS specification requires a line terminator at both ends of an RS-485 bus. ® If the TO-PASS telecontrol module is operated at one end of the line, the terminator must be added (e.g., directly in the D-Sub plug-in connector, or at the...
WAGO-TO-PASS® 761 Connect Devices 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 5.2.5.2 Serial Interface for MODBUS Current Sensor and PC Figure 20: Connection example for serial interface for MODBUS current sensor and PC Manual Version 1.0.0...
Commissioning WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Commissioning Installing the Operating Software ® Place the CD with the TO-PASS operating software in the CD drive of the The "Autostart" function is normally activated on set-up. If the set-up program does not start automatically, perform steps 2 to 6.
WAGO-TO-PASS® 761 Commissioning 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 ® Starting the TO-PASS Telecontrol Module Do not switch on yet! ® Do not switch on the TO-PASS telecontrol module until you are prompted to do so; do not insert the SIM card for this procedure.
Page 50
Commissioning WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 When generating a new configuration file, select the firmware version for the device that implements the required functionality as the first version in the Function selection field. The device versions, along with the associated enabling firmware indices are displayed to make selection easier.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Parameterizing General Settings Select the menu item File Settings for making general settings, such as type of > ® connection, interface or language for the TO-PASS operating interface. Figure 21: General settings...
Page 52
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 23: General settings Interface COM1 ... COMx Here, select the serial interface where the communication cable is connected with a RS-232 connection. Language ® English / Select the langauge for the TO-PASS operator interface here.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Reading Parameters from the Module ® After you have set the type of connection for communicating with the TO-PASS telecontrol module, you are then able to read out the parameters of the connected module.
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Identity ® Select the TO-PASS telecontrol module to be configured from the project tree; under it, select the Identity option. On the right side you will find the selection field for the function, the display field for the name, the input field for the telephone number, buttons and input fields for the PIN, roaming and prepaid and the input field for the alarm counter.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 24: Configuring the identity General Function selection You can redifine the firmware version in this selection field, that is to say the available scope of functions (e.g., to ensure compatibility with devices already in use).
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Addresses ® The TO-PASS telecontrol module can communicate with a maximum of four ® transmitters/receivers via GSM. Messages are sent by the TO-PASS telecontrol module as SMS; however, they can also be sent as an e-mail, fax or voice mail, as defined in configuration.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 25: Configuring the addresses Phone/Fax/Mail Address 1 ... Enter the target addresses in these fields: Address 4 Transmission as SMS: Enter the mobile phone number of the recipient.
Page 58
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 25: Configuring the addresses Online Host address In this field enter the host address for the Web portal for test purposes, e.g., "www.to-pass.com". Host port In this field enter the port for the Web portal (e.g., "80" for...
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Configuring Inputs and Outputs 7.5.1 Digital Inputs ® Select your TO-PASS telecontrol module from the left side of the project tree using the identifier. Select the input to be configured under Digital Inputs.
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Figure 25: Configuring digital inputs 5 … 8 (when provided) Table 26: Configuring of digital inputs Counters (only for digital inputs 1 … 4) Counters Check this box to use the selected digital input as a counter input.
Page 61
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 26: Configuring of digital inputs Alarm settings First value Check this box to have a message sent when the first limit is exceeded for upward counting or when the first lower limit is violated for downward counting.
Page 62
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 26: Configuring of digital inputs Deactivation text In this field enter the text to be contained in the message transmitted when the digital input has been reset, or when the counted value has violated the second limit.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.5.2 Multiplex Input You can configure digital inputs DI1 ... DI4 as multiplex inputs. These four inputs will then additionally be read in as a combination and intepreted as a binary number.
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.5.2.1 Multiplex Settings ® Select your TO-PASS telecontrol module from the left side of the project tree using the identifier. Select the Multiplex Settings option under Multiplex Input. The buttons for enabling multiplex operation and the selection of the recipients of the analog values to be transmitted are provided on the right side.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.5.2.2 Multiplex Alarm Text ® Select your TO-PASS telecontrol module from the left side of the project tree using the identifier. Select the Multiplex Table option under the Multiplex Input entry.
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.5.3 Analog Inputs ® Select your TO-PASS telecontrol module from the left side of the project tree using the identifier. Select the input to be configured under Analog Inputs. The parameters of the input are given on the right side.
Page 67
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 29: Configuring the analog inputs Alarm settings First value In this field enter the first limit for which a message is to be sent when this limit is violated (upper/lower limit) (see below).
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.5.4 Digital Outputs ® Select your TO-PASS telecontrol module from the left side of the project tree using the identifier. Select the output to be configured under the entry Digital Outputs.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Configuring Error Detectors ® The TO-PASS telecontrol module can transmit error messages to a maximum of four recipients. The recipients are informed either directly one after another or (if configured) after expiration of the time delay for acknowledgment.
Page 70
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 [4]. Click the [Internet] button to also transmit the message to a Web portal. In addition, you can also specify the analog values that are to be transmitted along with the error message.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.6.4 Acknowledgement Acknowledgment is the confirmation that a message has actually been sent to the ® recipient. Select the TO-PASS telecontrol module from the project tree using the identifier. Select the entry Acknowledgment under the option Special Functions.
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Transmission Repeat Times ® Select the TO-PASS telecontrol module from the project tree using the identifier. Select the entry Repeat times under the option Special Functions. The input fields for the Web interval, the Web outputs and the SMS interval and buttons for target addresses are located on the right side.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 32: Configuring the transmission repeat times Web settings Web interval In this field enter the cycle time in minutes to define the ® intervals that the TO-PASS telecontrol module is to send data to the Internet.
Page 74
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 32: Configuring the transmission repeat times SMS Settings SMS interval Here, enter the cycle time in minutes to define the intervals ® that the TO-PASS telecontrol module is to send data to the addresses defined under Address.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Time Adjustment ® Select the TO-PASS telecontrol module from the project tree using the identifier. Select the entry Acknowledgment under the option Time setting. The buttons for various settings pertaining to time adjustment are located on the right side.
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 MODBUS The MODBUS functionality facilitates connectivity for MODBUS interface- equipped devices. The devices must be configured as slave devices and are ® connected via PC interface. As a result, the TO-PASS telecontrol module operates as a master.
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.9.1 MODBUS Settings ® Select the TO-PASS telecontrol module from the project tree using the identifier. Select the MODBUS Settings option under the MODBUS entry. The buttons for the MODBUS format and the input field for the polling cycle time...
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.9.2 MODBUS Alarm When using the MODBUS functionality, an input of a MODBUS device can be defined that triggers an alarm when it assumes the high state (logical "1").
WAGO-TO-PASS® 761 Parameterizing 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.9.3 MODBUS Registers A maximum of 64 registers can be read from the connected MODBUS subscribers. The registers are compiled in four groups (1 ... 16, 17 ... 32, 33 ... 48, 49 ...
Parameterizing WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 7.10 Writing Parameters to the Module ® After you have adapted all parameters for the TO-PASS telecontrol module to your requirements, you have to write the parameters to the connected module.
WAGO-TO-PASS® 761 Operation 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Operation Remote Query of Process Values ® The TO-PASS telecontrol module offers two options for remote inquiry of the process values available: • Query via SMS ® • Query with the TO-PASS...
Operation WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 8.1.1 Remote Polling via SMS For remote polling via SMS, send an SMS containing the text "State" to the TO- ® PASS telecontrol module. ® The TO-PASS telecontrol module responds promptly with an SMS to your mobile phone containing all of the current process values.
WAGO-TO-PASS® 761 Operation 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 39: Counter status Status Explanation Digital input not configured as a counter. e:ZW Counter is active: Counter value. d:ZW Counter is not active: Counter value. o:ZW Counter overflow: Counter vlaue.
Operation WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 ® 8.1.2 Remote Polling using the TO-PASS Operating Program ® To display the process values with the TO-PASS operator program, select the menu item Visualization > Process values. The program establishes a link to the ®...
WAGO-TO-PASS® 761 Operation 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 8.1.2.1 Inputs/Outputs Press the [I/O] button to display the process values of the inputs and outputs. The process values displayed are valid if the on-line display is green. Figure 36: Visualization of the process values...
Operation WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 8.1.2.2 MODBUS Press the [MODBUS] button to display the MODBUS process values. The process values displayed are valid if the on-line display is green. Figure 37: MODBUS process values...
WAGO-TO-PASS® 761 Operation 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 8.1.2.3 Counters To display the counter process values, click the [Counter] button (possible only when inputs have been configured as counters). The process values displayed are valid when the on-line indicator is highlighted in green.
Operation WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Telecontrol ® TO-PASS telecontrol modules offer the option of influencing a process remotely with the help of their analog and digital outputs. There are two methods available: • Telecontrol via SMS ®...
WAGO-TO-PASS® 761 Operation 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 8.2.1 Telecontrol via SMS 8.2.1.1 Setting or Resetting a Digital Output To set or reset a digital output, send an SMS with the text that is entered under ®...
Operation WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 8.2.1.2 Changing the Counter Value or Status To change the value or the status of a counter, send an SMS containing the text "Counter" and the corresponding control commands (more than one can be sent) ®...
WAGO-TO-PASS® 761 Operation 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 ® 8.2.2 Telecontrol with the TO-PASS Operator Program ® To display the process values with the TO-PASS operator program, select the menu item Visualization > Process values. The program establishes a link to the ®...
Operation WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 8.2.2.1 Inputs/Outputs Press the [I/O] button to display the process values of the inputs and outputs. The process values displayed are valid if the on-line display is green. Figure 39: Visualization of the process values...
WAGO-TO-PASS® 761 Operation 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 8.2.2.2 Counters To display the counter process values, click the [Counter] button (possible only when inputs have been configured as counters). The process values displayed are valid when the on-line indicator is highlighted in green.
Operation WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Acknowledging Error Messages If a waiting time not equal to 0 has been set for the acknowledgment of error ® messages, the TO-PASS telecontrol modules expects an acknowledgment of error messages from the recipient.
WAGO-TO-PASS® 761 Operation 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Switching to Standby Standby authorization Switching standby on and off is only possible by subscribers whose telephone number has been entered in the address list! Using the "Standby" function, it is optional to change all messages sent by the ®...
Diagnostics WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Diagnostics Test Inputs and Outputs To test the inputs and outputs select the menu option Controller > Test I/O. The following window is displayed: Figure 41: Test inputs and outputs The process values of the inputs are displayed in the upper area and the process values of the outputs are displayed in the lower area.
WAGO-TO-PASS® 761 Diagnostics 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Testing the Counter Inputs To test the counter inputs, select the menu item Edit > Test counters. Figure 42: Testing counters The counter statuses are shown at the top of the window, while the counter values, the starting and end values and the limits are shown at the bottom.
Diagnostics WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Testing the Connection Direct serial link required ® The connection may only be tested with a direct serial link to the TO-PASS telecontrol module. To test the connection, select the menu option Edit > Test SMS/GPRS. The...
WAGO-TO-PASS® 761 Diagnostics 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Testing the Modem Direct serial link required ® The modem test may only be performed with a direct serial link to the TO-PASS telecontrol module. To test the mode, select the menu item Modem > Test.
To do this, enter "www.to-pass.com" as the Host address and the value "80" as the Host port. Enter "wago/saveTO-PASS.php" as the script name under Script (Values) and/or under Script (Logger). Enter the information for your SIM card provider for APN access, user name and password (see also Section “Parameter setting”...
WAGO-TO-PASS® 761 WAGO TO-PASS® Web 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.2 HTTP Request ® The HTTP method "POST" transmits the process image of the TO-PASS ® telecontrol module to the Internet to the WAGO TO-PASS portal. A data set consists of form data in the context of the request (header and data string).
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3 Data Sets To distinguish the structure of the incoming data sets, the new data sets are marked with a version variable. The variable is structured as “xx.yy”, while “xx”...
WAGO-TO-PASS® 761 WAGO TO-PASS® Web 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.1.1 Value Script FW 2.20 (Standard) Table 42: Data format for value script FW 2.20 (Standard) Index Variable Contents Format Identity Identity[8];Serial number[5] Parameter Cycle time[4];Provider[5];Alarm counter[2] Date, time YY/MM/DD,hh:mm:ss;...
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.1.1.1 Example of Value Script FW 2.20 (Standard) To improve readability, line breaks have been inserted. ID=TO-PASS;12345 &PA=0000;home ;99 &TI=11/05/05,14:34:21 &D1=1;0&D2=0;0&D3=0;0&D4=0;0&D5=0;0&D6=0;0&D7=0;0&D8=0;0 &A1=+00.00;mA;0&A2=+00.00;mA;0&A3=+00.00;mA;0&A4=+00.00;mA;0 &A5=+00.00;mA;0&A6=+00.00;mA;0&A7=+00.00;mA;0&A8=+00.00;mA;0 &US=Hello &PO=123155.000,5217.9742N,00855.2710E,4.4,74.9,2,214.30,6.0,3.2, 110505.00 Manual...
WAGO-TO-PASS® 761 WAGO TO-PASS® Web 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.1.2 Value Script FW 2.31 (Extended) Due to extended functionalities, the value script has been extended to include a version designation ("01.01") as well as supply voltage, output values and GPS information.
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 44: Meaning of flag Flag 1 Flag 2 Flag 3 Flag 4 Flag 5 Flag 6 Flag 7 Flag 8 Flag 1 0: GPS has not been started.
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.1.3 Value Script FW 2.33 (Counter Inputs) The counter inputs have resulted in counter data, signal quality and an indicator being added to the display for the value script ("SV=02.00") and to an update of the MODBUS registers and analog outputs.
WAGO-TO-PASS® 761 WAGO TO-PASS® Web 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 The counter status shows the last change that has occurred since the last value script transmission, or after a system start (independent of the SMS and logger status).
WAGO-TO-PASS® 761 WAGO TO-PASS® Web 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.2 Logger Script Data transmission to the logger script is activated via cyclical transmission repetitions (Web interval). Data packet information contains the logger's values that have not been acknowledged yet.
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.2.1 Logger Script Standard In the standard format, 10 logger entries are transmitted in a packet. Each entry consists of a compressed data set of 14 binary bytes, which are attached to the hexadecimal character string of the variable.
WAGO-TO-PASS® 761 WAGO TO-PASS® Web 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.2.1.2 Example for Logger Script Standard To improve readability, line breaks have been inserted. ID=TO-PASS;12345 &PA=0005;home ;99 &TI=11/05/05,14:36:11 &LO= 092D4AD100000000000000000000 562D4AD123000000000000000000 3F2D4AD12A000000000000000000 562D4AD137000000000000000000 562D4AD159000000000000000000 562D4AD164000000000000000000 3F2D4AD169000000000000000000 562D4AD19A000000000000000000...
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.2.2 Logger Script Extension The logger script has been updated due to extended functionalities. The “02.00” version designation has been assigned due to major modifications. Table 49: Data format for logger script FW 2.31 (extended)
WAGO-TO-PASS® 761 WAGO TO-PASS® Web 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.2.2.1 Data Format for LIOx Variable Table 50: Data format for logger script FW 2.31 (extended), Variable LIOx Index Contents Format Message counter Message counter[4]; Event (cyclic logger) Event[2];...
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.2.2.3 Example for Logger Script Extension To improve readability, line breaks have been inserted. ID=TO-PASS(Ext);12345 &LV=02.00 &PA=0005;home ;99 &TI=11/05/05,08:38:22 &LIO1=0019;09;11/05/05,08:33:44;00;000;000;000;000;000;000;000;000 ;C4A;0;000;000 &LPD1=10;08/01/01,06:33:35;274;0;0;N;0;0;W;00;0;0;0;0;0;0;0 &LIO2=001A;3F;11/05/05,08:34:02;00;000;000;000;000;000;000;000;000 ;BA2;0;000;000 &LPD2=10;08/01/01,06:33:55;274;0;0;N;0;0;W;00;0;0;0;0;0;0;0 &LIO3=001B;56;11/05/05,08:34:26;00;000;000;000;000;000;000;000;000 ;B89;0;000;000 &LPD3=C0;11/05/05,06:34:25;276;C41;2600;N;216;1621;E;0C;4D34;3;26A...
Page 117
WAGO-TO-PASS® 761 WAGO TO-PASS® Web 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 The calculations for longitudes/latitudes (see below) refer to the format as transmitted in the NMEA data (ccmm.mmmm with cc = degree, mm.mmmm = Angular minute). The cc.mm format is used to indicate the direction (also according to NMEA definition).
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.2.3 Logger Script FW 2.33 (Counter Inputs) The counter inputs have resulted in counter data and an indicator being added to the display for non-set time (operating hours) to the logger script ("LV=02.01").
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.3.2.4 Time Request Script FW 2.33 If time adjustment is to take place via the Internet, a time request script is transmitted on system start in order to adjust the time when a reply is received.
The data string must contain the following text: “Values stored” or “Values stored:YY/MM/DD,hh:mm:ss”. Date and time are optional and are required only if the time of the WAGO TO- ® PASS telecontrol module is to be set via the Web portal.
WAGO TO-PASS® Web WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 10.4.1 Example of HTTP Response The HTTP response consists of both header and data string, which are separated by an empty line (<CR><LF> = Carriage Return + Line Feed).
Figure 2: Antenna connection ................19 Figure 3: Terminal assignment for operating voltage ........... 20 Figure 4: Example of the WAGO shield connecting system ........ 23 Figure 5: Terminal assignment for digital inputs ..........24 Figure 6: Counter input pin assignments ............... 25 Figure 7: Terminal assignment for analog inputs ..........
List of Tables WAGO-TO-PASS® 761 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 List of Tables Table 1: Number notation ..................10 Table 2: Font conventions ..................10 Table 3: Overview of functions ................17 Table 4: Terminal assignment for operating voltage ..........20 Table 5: WAGO ground wire terminals ..............
Page 125
WAGO-TO-PASS® 761 List of Tables 761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485 Table 49: Data format for logger script FW 2.31 (extended) ......114 Table 50: Data format for logger script FW 2.31 (extended), Variable LIOx ..115 Table 51: Data format for logger script FW 2.31 (extended), Variable LPDx ... 115 Table 52: Data format, logger script extension, Variable LCDx ......
Page 126
Pos : 48 /D okumentation allgemei n/Einband/Einband H andbuc h - R üc kseite @ 9\mod_1285229376516_21.doc x @ 64944 @ @ 1 WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 • D-32385 Minden Hansastraße 27 • D-32423 Minden Phone: +49/5 71/8 87 – 0 Fax: +49/5 71/8 87 –...