84
Parameterizing
7.9.3
MODBUS Registers
A maximum of 64 registers can be read from the connected MODBUS
subscribers. The registers are compiled in four groups (1 ... 16, 17 ... 32, 33 ... 48,
49 ... 64).
Select the TO-PASS
Select the option MODBUS Registers for the corresponding group under the
MODBUS entry.
The input fields for the addresses of the registers to be polled are provided on the
right side. The input fields are identical for all register groups:
Figure 38: Configuring the MODBUS registers
Table 40: Configuring the MODBUS registers
Variable table: module/register/name (input register):
Register 1* 16,
(Registers 17 ...
32,
Registers 33 ... 48,
(Registers 49 ...
64)
761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485
®
telecontrol module from the project tree using the identifier.
Enter the address of the MODBUS subscriber in the Module
column and the number of the register to be polled in the
Register column. You can enter a designator in the Name
(input register) column.
Each value is read in as a 16-bit value and a maximum of 64
values can be read.
WAGO-TO-PASS® 761
Manual
Version 1.0.0