Analog Inputs; Digital Outputs; Analog Outputs; Data And Event Logger - WAGO -TO-PASS 761 Manual

Telecontrol module compact, 8 ai, web, telecontrol module for fault detection/indication, monitoring and remote control
Hide thumbs Also See for WAGO-TO-PASS 761:
Table of Contents

Advertisement

36
Device Description
3.6.8

Analog Inputs

Table 22: Technical Data Analog Inputs

Number of inputs
Input current
Internal resistance
Resolution
Measuring error (25°C)
Temperature coefficient
3.6.9

Digital Outputs

Table 23: Technical Data Digital Outputs

Number of outputs
Output type
Output current
Type of load
Energy dissipation W
(unique switching off)
3.6.10

Analog Outputs

Table 24: Technical Data Analog Outputs

Number of outputs
Output current
Load impedance
Resolution
Measuring error (25°C)
Temperature coefficient
3.6.11

Data and Event Logger

Table 25: Technical Data Data and event logger

Memory type
Memory size
761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485
max.
Without configured
counters
With configured
counters
WAGO-TO-PASS® 761
8
0/4 mA ... 20 mA
Approx.. 200 Ω / 20 mA
12 bit
< ±1 % of the full scale value
< ±0.1 % / K of the full scale value
4
Semiconductor outputs
0.5 A/30 V DC, short-circuit protected
Resistive, inductive, lamps
125 mJ;
2
L
= 2 * W
/ I
max
max
2
0/4 mA ... 20 mA
≤ 600 Ω
12 bit
< ±1 % of the full scale value
< ±0.1 % / K of the full scale value
Ring memory
4096 process images
2048 process images
Manual
Version 1.0.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

761-217