WAGO-TO-PASS® 761
761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485
7.10

Data Logger

Select the TO-PASS
Select the entry Data Logger under the option Special Functions. The input field
for the cycle time and a button for calculating the average value are located on the
right side.

Figure 39: Configuring the data logger

Table 41: Configuring the data logger

Settings
Cycle time
Average value
Manual
Version 1.0.0
®
telecontrol module from the project tree using the identifier.
In this field enter the cycle time in minutes at which the
process image is to be saved.
The process image is specific to devices and firmware used
and is described in the Section "Operation – Data Logger
(DSP)".
The data logger is a cyclic buffer; i.e., when the buffer is full,
the oldest process images are overwritten (F.I.F.O). The size
of the data logger depends on the device used and is specified
in the technical data sheet.
Press the [On] button to switch average value calculation on
or off.
If average value calculation is on, the analog input values
read at a sampling rate of 10 ms are added within a cycle
time. The total is than divided by the number of values read
in the cycle time and saved.
Parameterizing
85