WAGO-TO-PASS® 761
761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485
7.5.3
Analog Inputs
Select your TO-PASS
using the identifier. Select the input to be configured under Analog Inputs. The
parameters of the input are given on the right side.
The buttons and input fields are identical for all analog inputs:
Figure 30: Configuring the analog inputs
Table 32: Configuring the analog inputs
Standardization
Input signal
Min. value
Max. value
Unit
Manual
Version 1.0.0
®
telecontrol module from the left side of the project tree
Use these buttons to select the input signal for the sensor
connected to the TO-PASS
In this field enter the starting value from which the given
value is normalized. This value corresponds to the minimum
input current value of 0 mA or 4 mA.
In this field enter the end value up to which the given value is
normalized. This value corresponds to the maximum input
current 20 mA.
In this field enter the unit with a maximum of 5 characters
with which the normalized process value is to be transmitted.
Parameterizing
®
telecontrol module.
69