Technical data
13.2.

Technical data Actuator controls

Features and functions
Explosion protection
Certificates and standards
Particular conditions of use
Power supply
External supply of the electronics
(option)
Rated power
Control inputs
Control voltage/current consumption
for control inputs
84
SAVEx 07.2
SAVEx16.2/SARVEx 07.2
Refer to name plate
Certificates are attached to the device. All standards applied and their respective issues are indicated
on these certificates.
The particular conditions of use are listed on the certificates supplied.
Standard voltages AC:
3-phase AC
Voltages/frequencies
Volt
220
240
Hz
50
Permissible variation of mains frequency: ± 5 %
Permissible variation of mains voltage: ± 10 %
30 % for maximum 10 seconds within a range of 380 V
If required, the motor speed will be reduced down to nominal speed depending on the load of the
actuators used
A low mains voltage increases the mains current consumption; a higher mains voltage reduces the
mains current consumption
The torque limits of the actuators used might be decreased for a short time, if applicable
24 V DC: +20 % / 15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
For external electronics supply, the power supply of integral controls must have an enhanced isolation
against mains voltage in compliance with IEC 61010-1 and the output power be limited to 150 VA.
The actuator controls are designed for the rated power motor power, refer to motor name plate
6 digital inputs: OPEN, STOP, CLOSE, EMERGENCY (via opto-isolator, thereof OPEN, STOP, CLOSE
with one common and EMERGENCY without common, respect minimum pulse duration for modulating
actuators.
Standard
24 V DC, current consumption: approx. 10 mA per input
Options:
48 V DC, current consumption: approx. 7 mA per input
60 V DC, current consumption: approx. 9 mA per input
100 V
125 V DC, current consumption: approx. 15 mA per input
100 V
120 V AC, current consumption: approx. 15 mA per input
All input signals must be supplied with the same potential.
SARVEx16.2 Control unit: electronic (MWG)
1-phase AC
Voltages/frequencies
380
480
Volt
60
50
60
Hz
ACVExC 01.2 Non-Intrusive
110
120
220
50
60
50
480 V with the following restrictions:
240
60