Commissioning (basic settings)
Information
10.3.

Output speed (internal): set

Select main menu
Select parameter
68
SAVEx 07.2
SAVEx16.2/SARVEx 07.2
12. Save new value via
The tripping torque is set.
13. Back to step 4 (CLOSED or OPEN): Press
The following fault signals are issued if the torque setting performed has been reached
in mid-travel:
In the display of the local controls: Status indication S0007 Fault =
Torque fault OPEN or Torque fault CLOSE
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:
1.
either by an operation command in the opposite direction.
-
For Torque fault OPEN: Operation command in direction CLOSE
-
For Torque fault CLOSE: Operation command in direction OPEN
2.
or, in case the torque applied is lower than the preset tripping torque:
-
in selector switch position Local control (LOCAL) via push button RESET.
-
in selector switch position Remote control (REMOTE):
-
via a digital (I/O interface) with the Reset command if a digital input
is configured for RESET signal.
This setting is only required if an internally specified speed is set as speed source:
Sp. source... = Internal 1/Internal 2/Internal 3/Internal 4
Sp. source... = 2 DigIn: "Internal (1-4)"
If the actuator is controlled via an external speed source, the internal speed values
described here will not have an impact on the operation behaviour.
For further information on setting the speed source refer to Manual (Operation and
Setting):
Customer settings M0041
Speed functions M1699
Speed internal1 M1930
Speed internal2 M1931
Speed internal3 M1932
Speed internal 4 M1933
Speed rem. min. M1936
Speed rem. max M1937
Default value: according to order data
Setting range: The adjustable speed range is indicated on the actuator name plate.
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: Press
Display indicates: Speed internal1
SARVEx16.2 Control unit: electronic (MWG)
Save.
Esc.
to parameter, or
and enter ID, e.g.: M1930.
ACVExC 01.2 Non-Intrusive