Commissioning (basic settings)
Information
10.1.12. Hysteresis for signalling intermediate positions: set
Example
10.2.
Torque switching: set
Information
66
SAVEx 07.2
SAVEx16.2/SARVEx 07.2
Figure 75: Signal behaviour of positions
The set signal behaviour is valid for all positions.
The hysteresis determines the tripping point.
Parameter Position 4 M1153 is set to 180° (50 % of the travel).
Parameter Hysteresis M1148 is set to 3.0°.
Figure 76: Switching behaviour for signalling behaviours B, C, D and hysteresis 3.0°.
P1
Switch-on point ( ● )
P2
Switch-off point (○)
pT
Pulse duration = 2 times XT + hysteresis
Required user level: AUMA (6).
Customer settings M0041
Multiport valve M1140
Hysteresis M1148
Default values: 0.5° for all 16 intermediate positions
Setting range:0.0° to 5.0° (degree)
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
The torque switches may also trip during manual operation.