10.1.8.

Dead band

10.1.9.

Correction of inertia

10.1.10. Backlash compensation

10.1.11. Signalling behaviour of positions: set/check

No signal
C________|¯¯¯¯¯¯¯¯O
C¯¯¯¯¯¯¯¯¯|_______O
C_______|¯|_______O
SARVEx16.2 Control unit: electronic (MWG)
The dead band prevents operation to a new setpoint position within a specified band.
Required user level: Specialist (4) or higher.
Customer settings M0041
Multiport valve M1140
Dead band M1145
Default value: 0.00°
Setting range: 0.00 – 36.0° (degrees)
Due to reaction times and inertia, each Multiport valve has a specific inertia. This
can be compensated by inertia correction.
Required user level: Specialist (4) or higher.
Customer settings M0041
Multiport valve M1140
Overrun M1656
Default value: 0.00°
Setting range: 0.00° – 10.0° (degrees)
Adjustable backlash compensation of the overall system including valve coupling.
Required user level: Specialist (4) or higher.
Customer settings M0041
Multiport valve M1140
Backlash comp. M1146
Default value: 0.00°
Setting range: 0.00 – 36.0° (degrees)
Reaching of a point (valve port) can be signalled:
via indication lights (LEDs) of the local controls or
(refer to chapters <Indications> <Indication lights>)
via output contacts
(refer to chapters <Indications> <Assignment of outputs>)
Signal behaviour, this means the signal behaviour upon reaching a position, is set
via parameter MPV sign. beh. 1.
Customer settings M0041
Multiport valve M1140
MPV sign. beh. 1 M1147
Default value: No signal
Setting values:
A: Signal behaviour Off. Position is not signalled.
B: Signal is active from reaching the position up to 360°.
C: Signal is active from 0° until the position is reached.
D: When passing the position, a pulse signal is issued. The pulse range (range +/
around the pivot point) depends on the set hysteresis.