Commissioning (basic settings)
10.1.7.

Operate to position from Remote

Example
Example
64
SAVEx 07.2
SAVEx16.2/SARVEx 07.2
Symbol
Set positions (of valve ports)
P
(P1, P2, ...) selected position (1, 2, ...)
/ N/A
No position has been selected.
E2
Actual position value
Homeport (zero point) set
No homeport (zero point) has been set
To interrupt an operation (triggered operation command):
→ Select "
/ N/A " during operation and confirm via Ok (push button
actuator stops in its current position.
For direct operation to position from remote, make sure that selector switch position
Remote control (REMOTE) is selected.
Operation to position via digital inputs
An input (DIN) must be configured for each position (valve port).
Configuration of digital inputs
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital inputs M0116
DIN4 input to operate to position 1 selecting the shortest path:
Parameters: Signal DIN 4 M0118 = Intermediate pos. 1
Setting values for digital inputs (DIN)
Intermediate pos. 1 to
Intermediate pos. 16
MPV: CW Position 1 to
MPV: CW Position 10
MPV: CCW Position 1 to
MPV: CCW Position 10
MPV DriveCW
MPV DriveCCW
Command "Next position"
Required user level: Specialist (4) or higher.
A digital input is used to select the desired operation to the next port including the
direction of operation. Thus, up to 16 ports can be approached in both directions,
even without fieldbus connection with only 2 inputs.
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Parameter Signal DIN 1 M0117:
Next position CW = clockwise
Next position CCW = counterclockwise
Self-retaining when leaving the factory in both direction (cw and ccw).
SARVEx16.2 Control unit: electronic (MWG)
ACVExC 01.2 Non-Intrusive
Operation behaviour for input control
Operation to defined position while selecting the
shortest path
Operation to defined position in clockwise direction
Operation to defined position in counterclockwise
direction
Actuator operates in clockwise direction (without
stop at any position).
Actuator operation in counterclockwise direction
(without stop at any position).
). The