SARVEx16.2 Control unit: electronic (MWG)
Valve damage due to excessive tripping torque limit setting!
The tripping torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Default value: According to order data
Setting range: Torque range according to actuator name plate
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: press
Display indicates: Trip torque CLOSE
4.
Use
Up ▲ Down ▼ to select:
▶ Trip torque CLOSE
▶ Trip torque OPEN
The black triangle ▶ indicates the current selection.
5.
Press Ok.
Display shows the set value.
The bottom row indicates: Edit Esc
6.
Press Edit.
Display indicates:
-
Specialist (4) → continue with step 7
-
in bottom row Up ▲ Down ▼ Esc → continue with step 11
7.
Up ▲ Down ▼ to select user:
Use
Information: Required user level: Specialist (4) or higher.
The symbols have the following meanings:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
8.
Press Ok.
Display indicates: Password 0***
9.
Enter password (→ enter password).
Display shows the set value.
The bottom row indicates: Edit Esc
10.
Press Edit.
11. Enter new value for tripping torque via
Information: The adjustable torque range is shown in round brackets.
Commissioning (basic settings)
to parameter, or
and enter ID M0088.
Up ▲ Down ▼.
67