Technical Data Actuator Controls - AUMA SAV 07.2 Operation Instructions Manual

Multi-turn actuators
Hide thumbs Also See for SAV 07.2:
Table of Contents

Advertisement

SAV 07.2
SAV 16.2 / SARV 07.2
ACV 01.2 HART
Service conditions
Corrosion protection
Coating
Colour
Lifetime
Noise level
14.2.

Technical data Actuator controls

Features and functions
Power supply
External supply of the electronics
(option)
Rated power
Control and feedback signals
Additional input signals for
HART interface (option)
Control voltage/current consumption
for control inputs
Status signals
SARV 16.2 Control unit: electronic (MWG)
Standard:
KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option:
KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Double layer powder coating
Two-component iron-mica combination
Standard:
AUMA silver-grey (similar to RAL 7037)
Option:
Available colours on request
AUMA multi-turn actuators meet or exceed the lifetime requirements of EN 15714-2. Detailed information
can be provided on request.
< 72 dB (A)
Standard voltages AC:
3-phase AC
Voltages/frequencies
Volt
220
240
Hz
50
60
Permissible variation of mains frequency: ±5 %
Permissible variation of mains voltage: ±10 %
30 % for maximum 10 seconds within a range of 380 V
If required, the motor speed will be reduced down to nominal speed depending on the load of the
actuators used
A low mains voltage increases the mains current consumption; a higher mains voltage reduces the
mains current consumption
The torque limits of the actuators used might be decreased for a short time, if applicable
24 V DC: +20 % / 15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
For external electronics supply, the power supply of integral controls must have an enhanced isolation
against mains voltage in compliance with IEC 61010-1 and the output power be limited to 150 VA.
The actuator controls are designed for the nominal motor power, refer to motor name plate
Via HART interface
Device category: Actuator
Analogue 4
20 mA setpoint with digital HART communication
2 free analogue inputs (0/4
-
Signal transmission is made via HART interface
Inputs OPEN, STOP, CLOSE, EMERGENCY, I/O interface, (via opto-isolator thereof OPEN, STOP,
CLOSE with one common and EMERGENCY, I/O interface respectively without common)
-
Control inputs: OPEN, STOP, CLOSE, EMERGENCY
-
I/O interface: Selection of control type (HART or additional input signals)
Standard
24 V DC, current consumption: approx. 10 mA per input
Options:
48 V DC, current consumption: approx. 7 mA per input
60 V DC, current consumption: approx. 9 mA per input
100
125 V DC, current consumption: approx. 15 mA per input
100
120 V AC, current consumption : approx. 15 mA per input
All input signals must be supplied with the same potential.
Via HART interface
1-phase AC
Voltages/frequencies
380
480
Volt
50
60
Hz
480 V with the following restrictions:
20 mA), 4 free digital inputs
Technical data
110
120
220
240
50
60
50
60
83