Hart Terminal Compartment: Close (Version With Hart Connection Board) - AUMA SAV 07.2 Operation Instructions Manual

Multi-turn actuators
Hide thumbs Also See for SAV 07.2:
Table of Contents

Advertisement

Electrical connection
6.2.6.

HART terminal compartment: close (version with HART connection board)

36
SAV 07.2
SAV 16.2 / SARV 07.2
Figure 33: Close HART terminal compartment
[1]
Cover (HART terminal compartment)
[2]
Screws for cover
[3]
O-ring
[4]
Cable entries for HART cables
[5]
Blanking plug
1.
Clean sealing faces of cover [1] and housing.
2.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the sealing faces.
3.
Check whether O-ring [3] is in good condition, correctly insert O-ring.
4.
Fit cover [1] and fasten screws [2] evenly crosswise.
5.
Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
SARV 16.2 Control unit: electronic (MWG)
ACV 01.2 HART