AUMA SAV 07.2 Operation Instructions Manual page 35

Multi-turn actuators
Hide thumbs Also See for SAV 07.2:
Table of Contents

Advertisement

SAV 07.2
SAV 16.2 / SARV 07.2
ACV 01.2 HART
SARV 16.2 Control unit: electronic (MWG)
Table 16:
XM 3-pole: Monitoring HART signal "Actuator"
Pin
Signal name
1
AIN+_H
2
Shield (drain)
3
AIN-_H
Connection assignment for "Current Output" device category
Table 17:
X2, screw-type terminal, 3-pole: analogue connection with HART signal ("Current output")
Pin
Signal name
1
AOUT+_H
2
Shield (drain)
3
AOUT-_H
Table 18:
J: Jumper for shield
Item
Position
1
Jumper from CAP to SHIELD
2
Jumper from horizontal level
to SHIELD
3
Jumper from OFF to SHIELD
Table 19:
XM 3-pole: Monitoring"Current Output" HART signal
Pin
Signal name
1
AIN+_H
2
Shield (drain)
3
AIN-_H
Signal type
Explanation/function
Current with HART
Positive (analogue) input (target value) with HART
signal following overvoltage protection
Not used on internal sub-assembly
Current with HART
Negative (analogue) input (target value) with HART
signal following overvoltage protection
Signal type
Function
Current with HART
Positive (analogue) output (target value) with HART
signal
Shield (EMC protec-
Wire or shield of infeed cable
tion)
Current with HART
Negative (analogue) output (target value) with HART
signal
Function
Shield via capacitor (2.2 nF/200 V) to PE
Shield directly to PE (default)
Shield not to PE (not recommended)
Signal type
Explanation/function
Current with HART
Positive (analogue) input (target value) with HART
signal
Following overvoltage protection
Not used for "monitoring"
Current with HART
Negative (analogue) input (target value) with HART
signal
Following overvoltage protection
Electrical connection
35