Commissioning (basic settings)
10.4.

HART address (slave address): set

Select main menu
Set HART address
10.5.

Output speed (internal): set

62
SAV 07.2
SAV 16.2 / SARV 07.2
HART address adaptation is only required for multidrop operation. Without multidrop
operation, address 0 must be set.
Customer settings M0041
HART M1238
Address M1253
Default value: 0
Setting range: 0
63
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
(by clicking through the menu)
or press
Display indicates: Address
4.
Press
Ok.
Display shows the set address.
5.
The bottom row of the display indicates:
Edit→ continue with step 6
Up ▲ Down ▼ → continue with step 10
6.
Press
Edit.
Display indicates: Observer (1)
7.
Select access level via
black triangle: ▶ = current setting
white triangle: ▷ = selection (not yet saved)
Information: Required access level: Specialist (4) or higher
8.
Press
Ok.
Display indicates: Password 0***
9.
Enter password (→ enter password).
Display shows the set address.
10. Enter new address via
Information: The address range is displayed in round brackets on the screen.
11. Confirm selection via
The HART address setting is complete.
This setting is only required if an internally specified speed is set as speed source:
Sp. source... = Internal 1/Internal 2/Internal 3/Internal 4
Sp. source... = 2 DigIn: "Internal (1-4)"
If the actuator is controlled via an external speed source, the internal speed values
described here will not have an impact on the operation behaviour.
For further information on setting the speed source refer to Manual (Operation and
Setting):
Customer settings M0041
SARV 16.2 Control unit: electronic (MWG)
and enter ID M0098 (direct selection)
Up ▲ Down ▼ resulting in the following significations:
Up ▲ Down ▼.
Save.