Torque Switching: Set - AUMA SAV 07.2 Operation Instructions Manual

Multi-turn actuators
Hide thumbs Also See for SAV 07.2:
Table of Contents

Advertisement

Commissioning (basic settings)
User login
Change settings
10.2.

Torque switching: set

Information
Select main menu
Select parameter
58
SAV 07.2
SAV 16.2 / SARV 07.2
6.
Press
Edit.
Display indicates: ▶ Specialist (4)
7.
Use
Up ▲ Down ▼ to select user:
Information: Required user level: Specialist (4) or higher
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
8.
Press
Ok.
Display indicates: Password 0***
9.
Enter password (→ enter password).
The screen indicates the pre-set type of seating (▶Limit or ▶Torque) by means
of a black triangle ▶.
10. Use
Up ▲ Down ▼ to select new setting.
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
11. Confirm selection via
The setting for the type of seating is complete.
12. Back to step 4 (CLOSED or OPEN): Press
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
The torque switches may also trip during manual operation.
Valve damage due to excessive tripping torque limit setting!
The tripping torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Default value: According to order data
Setting range: Torque range according to actuator name plate
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: press
Display indicates: Trip torque CLOSE
SARV 16.2 Control unit: electronic (MWG)
Save.
Esc.
to parameter, or
and enter ID M0088.
ACV 01.2 HART