Advertisement

Electrical connection
6.2.5.

HART cables: connect

Connection boards
34
SAV 07.2
SAV 16.2 / SARV 07.2
Figure 32: Variants of HART connection boards
[X]
Shielding clamp
[XM] Connection for HART modem
[X1/2] 4
20 mA HART cable
[J]
Jumper for shield
Table 13:
Variant
D40.03
D40.04
1)
Label with article number on connection board
Connection assignment for "Actuator" device category
Table 14:
X1, screw-type terminal, 3-pole: analogue connection with HART signal ("Actuator")
Pin
Signal
1
AIN+_H
2
Shield (drain)
3
AIN-_H
Table 15:
J: Jumper for shield
Item
Position
1
Jumper from CAP to SHIELD
2
Jumper from horizontal level
to SHIELD
3
Jumper from OFF to SHIELD
SARV 16.2 Control unit: electronic (MWG)
Device category
Actuator
Current Output
Signal type
Function
Current with HART
Positive (analogue) input (target value) with HART
signal
Shield (EMC protec-
Wire or shield of infeed cable
tion)
Current with HART
Negative (analogue) input (target value) with HART
signal
Function
Shield via capacitor (2.2 nF/200 V) to PE
Shield directly to PE (default)
Shield not to PE (not recommended)
ACV 01.2 HART
1)
AUMA art. no. on label
Z117.962/01
Z117.962/02