Technical data
Electromechanical control unit
Limit switching
Torque switching
Switch contact material
Position feedback signal, analogue
(option)
Mechanical position indicator (op-
tion)
Running indication
Heater in switch compartment
Electronic control unit
Non-Intrusive setting
Position feedback signal
Torque feedback signal
Mechanical position indicator
Running indication
Heater in switch compartment
Service conditions
Use
Mounting position
Installation altitude
Ambient temperature
Humidity
Enclosure protection according to
EN 60529
Pollution degree according to IEC
60664-1
82
SAV 07.2
SAV 16.2 / SARV 07.2
Counter gear mechanism for end positions OPEN and CLOSED
Turns per stroke: 2 to 500 (standard) or 2 to 5,000 (option)
Standard:
Single switch (1 NC and 1 NO) for each end position, not galvanically isolated
Options:
Tandem switch (2 NC and 2 NO) for each end position, switches galvanically isolated
Triple switch (3 NC and 3 NO) for each end position, switches galvanically isolated
Intermediate position switches (DUO limit switching), adjustable for each direction of op-
eration
Torque switching adjustable for directions OPEN and CLOSE
Standard:
Single switch (1 NC and 1 NO) silver contact (Ag) for each direction, not galvanically
isolated
Options:
Tandem switch (2 NC and 2 NO) for each direction, switches galvanically isolated
Standard:
Silver (Ag)
Options:
Gold (Au), recommended for low voltage actuator controls
Potentiometer or 0/4
20 mA (electronic position transmitter)
Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Blinker transmitter (option for modulating actuators)
Resistance type heater with 5 W, 24 V AC
Magnetic limit and torque transmitter (MWG)
Turns per stroke: 1 to 500 (standard) or 10 to 5,000 (option)
Via actuator controls
Via actuator controls
Continuous self-adjusting indication with symbols OPEN and CLOSED
Blinking signal via actuator controls
Resistance type heater with 5 W, 24 V AC
Indoor and outdoor use permissible
Any position
≤ 2 000 m above sea level
> 2,000 m above sea level on request
Standard:
30 °C to +70 °C
Options:
40 °C to +70 °C
60 °C to +60 °C
For exact version, refer to actuator name plate.
Up to 100 % relative humidity across the entire permissible temperature range
Standard:
IP68 with AUMA 3-phase AC motor
For special motors differing enclosure protection available (refer to motor name plate)
Option:
DS terminal compartment additionally sealed against interior of actuator (double sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
Depth of water: maximum 8 m head of water
Duration of continuous immersion in water: Max. 96 hours
Up to 10 operations during immersion
Modulating duty is not possible during immersion.
For exact version, refer to actuator name plate.
Pollution degree 4 (when closed), pollution degree 2 (internal)
SARV 16.2 Control unit: electronic (MWG)
ACV 01.2 HART