Electrical connection
6.2.2.

Cable connection

30
SAV 07.2
SAV 16.2 / SARV 07.2
3.
Insert cable glands [8] suitable for connecting cables.
The enclosure protection IP... stated on the name plate is only ensured if suit-
able cable glands are used.
Figure 27: Example: Name plate for enclosure protection IP68
4.
Seal unused cable entries [6] with suitable blanking plugs [7].
Table 12:
Terminal cross sections and terminal tightening torques
Designation
Power contacts
(U1, V1, W1, U2, V2, W2)
Protective earth connection
Control contacts
(1 to 50)
1.
Remove cable sheathing.
2.
Insert the wires into the cable glands.
3.
Fasten cable glands with the specified torque to ensure required enclosure
protection.
4.
Strip wires.
Controls approx. 6 mm, motor approx. 10 mm
5.
For flexible cables: Use wire end sleeves according to DIN 46228.
6.
Connect cables according to order-related wiring diagram.
SARV 16.2 Control unit: electronic (MWG)
Terminal cross sections
2
1.0
6 mm
(flexible)
2
1.5
10 mm
(solid)
2
1.0
6 mm
(flexible) with ring lugs
(PE)
2
1.5
10 mm
(solid) with loops
2
0.25
2.5 mm
(flexible)
2
0.34
2.5 mm
(solid)
ACV 01.2 HART
Tightening torques
1.2
1.5 Nm
1.2
2.2 Nm
0.5
0.7 Nm