Connectable Conductor Cross-Sections For Spring-Loaded Terminals - Siemens SINAMICS S120 Combi Equipment Manual

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

Cabinet design and EMC
12.7 Connection system
Example for dimensioning a power cable
Boundary conditions:
Module: S120 Combi 4 axes Power Module with 20 kW infeed
Rated input current at 400 V
Ambient temperature: 45 °C
Installation type: B2
Calculation/dimensioning:
With installation type B2 and a rated input current of 34 A
current-carrying capacity, a cable cross-section of 10 mm
With a derating factor of 0.91 for 45°C ambient temperature, the current-carrying capacity of
the selected power cable decreases to 36.4 A.
Result:
Under the given boundary conditions, a power cable with a cross-section of 10 mm
used.
12.7.4

Connectable conductor cross-sections for spring-loaded terminals

Table 12- 12 Spring-loaded terminals
Type: Spring-loaded terminal
1
Connectable conductor cross-
sections
Stripped length
Tool
306
: 34 A (from the technical data)
AC
Flexible
8 ... 9 mm
Screwdriver 0.4 x 2.0 mm
, from the table showing the
AC
is obtained.
2
0.08 ... 2.5 mm
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
can be
2
2