Conductor Cross-Sections, Braking Resistor And Pre-Charging Of Capacitor Module - Siemens 6SE7024-1EP85-0AA1 Operating Instructions Manual

Simovert masterdrives rectifier unit compact plus type
Table of Contents

Advertisement

Available languages

Available languages

05.2005
7.3
Conductor cross-sections, braking resistor and pre-
charging of capacitor module
NOTE
Unit
power
rating
Cross section
max.
VDE
AWG
[kW]
[mm²]
15
10
6
50
50
1/0
100
95
4/0
Siemens AG
6SE7087-2NP85-0AA0
SIMOVERT MASTERDRIVES
If the rectifier unit is mounted on a grounded mounting surface through
a conductive connection, the conductor cross-section of the protective
conductor can be the same as that of the supply-cable conductor.
Mains connection
Recommended fuses
gR (SITOR)
gL NH
[A]
3NE
[A]
3NA
40 1802-0 50 3820
160 1224-0 200 3140
250 1227-0 315 3252
Table 7-12
Conductor cross-sections, fuses, reactors
Operating Instructions
Main
c'tactor
Line reactor
4EP3700-4US
3TF44
4EU2451-2UA00
3TF50
4EU2551-5UA00
3TK52
Connecting-up
Connection of
braking
resistor,
capacitor
module
Cross section
max.
VDE
AWG
[mm²]
4
10
25
2
50
1/0
7-11