MODEL 2234 DIGITAL FLOW COMPUTER ___________________________

2.6.3 SUPPLEMENTARY STARTUP INSTRUCTIONS

This subsection is intended as a checklist of possible additional parameter entries
or modifications that may be required before placing the computer into service.
Where appropriate, references are made to more detailed explanations and
information contained in Section 3 of this manual.
Prior to placing the computer into service, confirm the values for each
measurement parameter (by using the Read Codes described in paragraph 3.6).
Note especially that density, pressure, temperature and differential pressure will
appear on the display as a varying value (VAR) unless the operator manually enters
a fixed (FXD) value. Should a specific transducer be inoperative or be unavailable,
a FXD value can be entered manually in lieu of the measured varying value per
paragraph 3.5.1.
2.6.3.1 LINE AND STATION TOTALIZING FACTORS
The Station or the Line Totalizing Factors may need to be different from the
o
factory-programmed factors of 10
. If so, determine the factors to be used per the
following example. Then enter the factors as described in paragraph 3.6.5.
The maximum instantaneous pulse rate output allowed by the computer is 25
pulses/second (25 unit volumes in pounds x 1/10, etc.).
However, a 25
pulse/second rate shortens the life of the Sodeco RG Series counter to 92.6 days
SECTION 2
43