MODEL 2234 DIGITAL FLOW COMPUTER ___________________________
B.
Temperature (TF) - Read Code 1
The measured temperature value, used by the computer to calculate flow rates and
flow totals, is displayed by using Read Code 1.
Fahrenheit. FXD values between -50 and 250 degrees Fahrenheit are acceptable.
C.
Static Pressure (PF) - Read Code 2
The measured static pressure value, used by the computer to calculate flow rates
and flow totals, is displayed by using Read Code 2. The pressure is displayed in
PSIA. FXD values between 0.0 and 5000 PSIA are acceptable.
D.
Line Differential Pressure (HWn) - Read Code 26n
The pressure differential, used by the computer to calculate mass rates and mass
totals, is displayed by Read Code 26n for the line selected (n). Pressure is
displayed in inches of water. FXD values between 0 and 1000 inches of water are
acceptable for testing purposes only.
SECTION 3
The display is in degrees
87