DANIEL 2234 Manual page 68

Table of Contents

Advertisement

__________________________ MODEL 2234 DIGITAL FLOW COMPUTER
Table 2-5. Error Code Diagnostic Chart
Error Code
Possible Cause
07
1. Pressure transducer
Line 5
not used for line 5.
differential
pressure
under range
2. Pressure out of
range, transducer
malfunctioning or mis-
calibrated, wiring
error.
08
1. Incorrect or
Temperature
malfunctioning
out of range
temperature probe
for density
being used for
calculation
computing density
NOTE: error
calculation.
code 8 is
disabled if 12
CMD is
enabled.
56
Check
1. Check VAR value
of read code 265
(H2O).
2. Check code number
entered for CONFIG
(system configuration),
command code 5.
1. Check that product
temperature is between
o
o
65
F and 166.9
F, read
code 1
(Continued)
Solution
1. Enter new
CONFIG code
number.
1. Check wiring.
2. Verify pressure.
3. Check transducer.
1. Check transducer
calibration.
SECTION 2

Advertisement

Table of Contents
loading

Related Products for DANIEL 2234