Install The Adapter Base Unit - Rockwell Automation Allen-Bradley 1715-AENTR User Manual

Redundant i/o system
Table of Contents

Advertisement

Install the Adapter Base
Unit
commercially available industrial uninterruptible power supplies (UPS). To
select a suitable power supply, calculate the overall system load that must be
powered (by using the following table), include any additional devices and add
a contingency allowance between 25...50%.
Component
Adapter
Digital input module
Analog input module
Digital output module
Analog output module
Power supply
The adapter base unit supports a pair of adapters. The adapter base unit has
connections for two power feeds, four Ethernet ports, and two adapters on the
front of the unit, and one I/O base connector on the right-hand side of the unit.
The connections for the adapters are commonly referred to as adapter slots.
To mount the 1715-A2A adapter base unit, follow these steps.
1. Place the 1715-A2A adapter base unit onto the DIN rails and position
them toward the left, leaving space for the I/O base units to the right.
2. Secure the adapter base unit onto the DIN rails by sliding the retaining
lever (below the base unit) to the left, as far as it goes, until it latches in
the locked position.
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Chapter 2
Installation Instructions
Power Requirement
8.0 W
4.0 W
4.0 W
3.0 W
3.6 W
Varies
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents