Chapter 6
Configure the Redundant I/O System
Table 38 - Fault/Program Action Parameters for Analog Output Duplex Module
Parameters
Ramp to Program Value
Program Mode Communication Failure Output State
Ramp Rate
198
Description
Check the Ramp to Program Value checkbox to transition the channel from the current value
to the program value (when in Program mode and limited by Ramp Rate). The default is
cleared.
Ramp to Program Value is enabled (excluding Hard Run mode) when the Program mode is set
to Use Program Value. Ramp to Program Value is dimmed (including Hard Run mode) when
the Program mode is set to Hold Last State.
Choose the output state when there is communication failure in Program mode (Program
mode or Fault mode). The default is Program mode.
Displays the Ramp Rate for the channel as it is displayed on the Module Properties dialog box
- Limits tab (1715-OF8I). To change this value, enter a Ramp Rate value on the Module
Properties dialog box - Limits tab (1715-OF8I).
Ramp Rate is enabled when online in the following:
• Program mode
• Remote Program mode
• Remote Run mode
12. Click OK.

Step 2: Add the Analog Output Module in Simplex Mode

1. Add the new module, see
2. Select the 1715-OF8I Analog Output Module, referring to
page
194, and click OK.
The General tab appears.
See figure on
3. Click Change, referring to
parameter settings.
4. Change Redundant to No to place the module in Simplex mode.
5. Click OK.
The Verify Module Properties dialog box appears. See
6. Click Yes.
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
page
177.
page 178
for General parameter settings.
Figure on page 190
step 2
on
for Module Definition
page 184.