Add the 1715-AENTR Adapter
to the I/O Configuration
Tree
IMPORTANT
The previous ControlLogix® Controller Organizer Tree shows a
1756-EN2TR module. The 1756-EN2TR can be used in Star (using
only one port), Device Level, or Linear ring topologies, or you can
use a 1756-EN2T module instead.
Once the project, controller and Ethernet module are configured, you are ready
to add the 1715 adapter. In this section, you do the following:
Add the 1715-AENTR adapter to the project.
Configure the adapter for the EtherNet/IP Network.

Step 1: Configure the Adapter for the EtherNet/IP Network

Plan IP addresses by doing the following:
You must use two IP addresses.
You must know the subnet mask for the Ethernet network the redundant
modules are to operate on.

Options for Setting the IP Addresses of 1715-AENTR Modules

You can set the IP address of the redundant AENTR modules in the adapter
base by using the following:
A BOOTP/DHCP utility. A BOOTP/DHCP utility is provided with the
Logix Designer application out of the box. See
Address on the BOOTP/DHCP Server on page
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Chapter 6
Configure the Redundant I/O System
Step 1: Assign an IP
123.
165