The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and
has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of
Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN
60079-0.
ATEX/IECEx Certification:
Certificate number: DEMKO 11 ATEX 7928686X
II 3G Ex nA IIC T4 Gc
Certificate number: IECEx UL 15.0032X
Ex nA IIC T4 Gc
The ambient temperature range is -25...+60 °C (-13...+140 °F) for all models.
Essential Health and Safety Requirements:
Met by compliance with the standards EN 60079-0: 2012 + A11:2013, EN 60079-15: 2010 and IEC 60079-0: Edition 6, IEC 60079-15:
Edition 4.
Special Conditions for Safe Use:
• All models: the ambient temperature range is -25 ...+60 °C (-13...+140 °F)
• Subject devices are to be installed in an ATEX/IECEx Certified, IP54, tool accessible enclosure that has been evaluated to the
requirements of
EN 60079-0: 2012 + A11:2013, EN 60079-15: 2010 and IEC 60079-0: Edition 6, IEC 60079-15: Edition 4. Enclosure is to be marked
with the following: "Warning - Do not open when energized". After installation of subject devices into the enclosure, access to
termination compartments shall be dimensioned so that conductors can be readily connected. Grounding conductor should
have a minimum cross sectional area of 3.31 mm² (12 AWG).
• Subject devices are for use in an area of not more than pollution degree 2 in accordance with IEC 60664-1.
• Subject devices are to use conductors with a minimum conductor temperature rating of 85 °C (185 °F).
• Subject devices are to be installed in the vertical orientation only.
WARNING:
• This equipment shall be mounted in an ATEX-certified enclosure with a minimum ingress protection rating of at least
IP54
(as defined in IEC60529) and used in an environment of not more than Pollution Degree 2 (as defined in IEC 60664-1)
when applied in Zone 2 environments. The enclosure must have a tool-removable cover or door.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140%
of the rated voltage when applied in Zone 2 environments.
• This equipment must be used only with ATEX certified Rockwell Automation Termination Assemblies.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or
other means provided with this product.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Enclosure must be marked with the following: 'Warning - Do not open when energized.' After installation of equipment
into the enclosure, access to termination compartments shall be dimensioned so that conductors can be readily
connected.

European Hazardous Location Approval

For more information, refer to
1715 Series Redundant I/O System - ATEX certificate,
publication 1715-CT002.
1715 Series Redundant I/O System - IECEx certificate,
publication 1715-CT001.
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Chapter 2
Installation Instructions
33