Chapter 6
Configure the Redundant I/O System
Table 35 - Configuration Parameters for the Analog Input Duplex Module
Parameters
Low Engineering
High Signal
High Engineering
192
Description
Enter the Low Engineering value for the channel (between -9999999...99999999). The default is 0.0. Low
Signal and Low Engineering values are shown in pairs.
Enter the High Signal value for the channel (between 0.0...20.0 mA). The default is 20.0 mA. This value
must be greater than the Low Signal value. High Signal and High Engineering values are shown in pairs.
Enter the High Engineering value for the channel (between -9999999...99999999). The default is 100.0.
High Signal and High Engineering values are shown in pairs.
9. Click OK.

Step 2: Add the Analog Input Module in Simplex Mode

Add a 1715-IF16 Analog Input module in Simplex mode to the project.
1. Add the new module, see
2. Select the 1715-IF16 module, see
The General tab appears.
See
Figure on page 178
3. Click Change, referring to
parameter settings.
4. Change Redundant to No to place the module in Simplex mode.
5. Click OK.
The Verify Module Properties dialog box appears. See
6. Click Yes.
A new General tab appears showing only one slot as available. The
module is now in Simplex mode.
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
page
177.
step 2
on
page 189.
for General parameter settings.
Figure on page 190
for Module Definition
page 184.