Appendix F
I/O Tag Definitions
Table 68 - 8-channel Digital Output, Duplex, Input
Tag Name
Data Type
ModBFieldPowerVoltage2
DINT
Ch
AB_1715_ChStatusStruc:I:0[8]

1715-IF16

Table 69 - 16-channel Analog Input, Simplex, Input
Tag Name
Fault
ChSimplex[0 - 15]
Data
Faults
RollingTimestamp
Status
Table 70 - 16-channel Analog Input, Duplex, Input
Tag Name
Fault
ChSimplex[0...15]
Data
Faults
284
Definition
Reports the voltage from the field power supply for the specified module and field power input.
Accuracy is ± 500mV
Current / Voltage
Status Array
This section describes the tags that are associated with the 1715-IF16 module.
Data Type
Definition
DINT, Binary
Module fault bit:
Array of structure
Array of 16 structures that represent the data and fault status for channels 0...15:
REAL
Input data status
DINT, bit-field
Channel fault status:
Bit
0
3
4
INT
Timestamp data
DINT, bit-field
Bit
8
Data Type
Definition
DINT, Binary
Module fault bit:
Array of structure
Array of 16 structures that represent the data and fault status for channels 0...15:
0 = Data
1 = Faults
REAL
Input data
DINT, bit-field
Channel fault status:
Bit
0
1
2
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Current: REAL
Reports the current for the channel in
milliamps and with an accuracy of ± 2
mA and ± 10% of measurement
Each element of the array
Voltage: REAL
comprises
Reports the channel voltage at the
output terminals in units of millivolts
and with an accuracy of ± 500 mV (The
voltage element cannot report values
below 0 mV
0 when one module is present and reporting valid data, OxFFF_FFFF
when no modules are present, no Logix connection exists, or reported
data is invalid.
Name
Description
Fault
0 = Good
1 = Circuit fault for this channel
Underrange
0 = Good
1 = Underrange detected
Overrange
0 = Good
1 = Overrange detected
Name
Description
GroupFault
0 = Good
1 = Any channel on the module is
faulted/failed
0 when one module is present and reporting valid data, OxFFF_FFFF
when no modules are present, no Logix connection exits, or reported
data is invalid.
Name
Description
Fault
0 = Good
1 = Circuit fault for this channel
ModAFault
0 = Good
1 = This channel on Module A is
faulted/failed
ModBFault
0 = Good