Precautions for HART Pass-Through in a Safety System

IMPORTANT
If you use HART Pass-Through in a safety system, take these
precautions:
• Observe the precautions in Precautions for HART in a Safety System
• Make sure that HART Pass-Through is enabled only under control of
the application.
• Make sure that HART Pass-Through is enabled only when necessary.
• Configure the application to generate an alarm if Hart Pass-Through
is enabled on any safety-critical channel of any module.

Installing the 1715-DTM

The 1715-DTM is the device type manage for the HART Pass-Through feature in
a 1715 system. It must be installed on the Windows computer which is running
the asset management system. For the PC specification refer to the Preface
chapter, Required Software.
To install the DTM, do the following:
1. Locate the file named setup.exe and run it.
2. If the computer onto which the DTM is being installed does not contain
the Microsoft packages required to support the DTM, the following
screen is displayed, in which case click Install.
3. Click Next.
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020