4.17.1. S.o.A1 - Defining the state of the analog output

Acronym
S.o.A1
ANALOG OUTPUT STATUS
The parameter shows and sets the state of analog retransmission output A1.
The active direct output corresponds to minimum with the minimum output value in voltage or current.
The active inverse output corresponds to minimum with the maximum output value in voltage or current.
The outputs can be forced so that they are always on or off.
Unit of measurement:
Options:
DIREC = Direct output
INVRS
OFF
ON
4.17.2. t.o.A1 - Defining the type of analog output
Acronym
t.o.A1
ANALOG OUTPUT TYPE
The parameter shows and sets the definition of analog output A1.
Unit of measurement:
Options:
20MA
4-20M
10V
2-10V
C.20MA = Custom Output 0...20 mA
C.4-20 = Custom Output 4...20 mA
C.10V
C.2-10 = Custom Output 2...10 V
4.17.3. F.o.A1 - Selecting the function assigned to the analog output
Acronym
F.o.A1
REFERENCE SIGNAL ANALOG OUTPUT
The parameter shows and sets the function assigned (retransmission of values) to analog output A1.
Unit of measurement:
Options:
NONE
HEAT
COOL
PV
SSP
SP
SP-PV
SERIA
if the Programmer function is enabled:
SLV.SP = Slaved setpoint
4.17.4. LO.A1 - Scale minimum
Acronym
LO.A1
LOW LIMIT ANALOG OUTPUT
The parameter shows and sets the scale minimum, which corresponds to minimum output value in voltage or current.
Unit of measurement:
Options:
-1999...9999
80208G_MHW_650-1250-1350_01-2017_ENG
Scrolling message
-
= Inverse output
= Forced output inactive (minimum voltage or current value)
= Forced output active (maximum voltage or current value)
Scrolling message
-
= Output 0...20 mA
= Output 4...20 mA
= Output 0...10 V
= Output 2...10 V
= Custom Output 0...10 V
Scrolling message
-
= No assigned function
= Heat control power
= Cool control power
= Process variable
= Active setpoint
= Local setpoint
= Deviation |SP-PV|
= Value set from serial line
Scrolling message
Scale points of quantity assigned to analog output.
4. CONFIGURATION
Submenu
Attributes
OUT.AN
R W
Submenu
Attributes
OUT.AN
R W
Submenu
Attributes
OUT.AN
R W
Submenu
Attributes
OUT.AN
R W
105

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

12501350

Table of Contents