Using A Function Of Digital Input 1 To Enable At Software On - gefran GFW ADV Configuration Manual

Advanced modular power controller
Hide thumbs Also See for GFW ADV:
Table of Contents

Advertisement

USING A FUNCTION OF DIGITAL INPUT 1 TO ENABLE
AT SOFTWARE ON
Software ON can be configured either by enabling a digital input or by writing via serial. Enabling by digital input 1
(diG) is common to all zones, whereas enabling via serial is specific for each individual zone.
The ON/OFF setting via serial is saved in eeprom (STATUS_W_EEP, address 698 bit 3) for resetting of the condition
at the next hardware power-on; use parameter P.On.t. to force software always ON or software always OFF at next power-on.
ON/OFF software
ON
OFF
STATE DIGITAL INPUT 1
28
Setting
dIG
13
ON
OFF
SERIAL WRITING
ON/OFF zone 1
ON
OFF
SERIAL WRITING
ON/OFF zone 2
ON
OFF
SERIAL WRITING
ON/OFF zone 3
Address for writing via serial
Access at 16 bits
word 305 bit 3
AND
logic
AND
logic
AND
logic
Access at 1 bit
bit 11
STATE
ON/OFF zone 1
STATE
ON/OFF zone 2
STATE
ON/OFF zone 3
80963B_MSW_GFW_11-2012_ENG