5.1.1.8. Analog input status
Acronym
App / GF_eXpress menu
Err
Analog input self-diagnosis status
Value
Meaning
0
No error
1
2
3
Error (*)
(*) The input is in error when a 4 ... 20 mA input is used and the current is less than 2 mA:
the Error status is generated and the power defined in FA.P is supplied.
5.1.2.
Load current value
Settings
5.1.2.1. Current reading correction offset
Acronym
App / GF_eXpress menu
o.tA
Current reading correction offset.
min...max: -99.9 ...99.9 A
5.1.2.2. Current reading low pass digital filter
Acronym
App / GF_eXpress menu
F.tA
Current reading digital filter.
min...max: 0.0 ...20.0 s
Status
5.1.2.3. Current reading scale minimum limit
Acronym
App / GF_eXpress menu
L.tA
Current reading scale minimum limit.
Status
Inputs CT input
Inputs CT input
Inputs CT input
819XX_MAN_GRM-H_11-2022_ENG_pag. 29
Attribute Retentive
Description
R
-
Attribute Retentive
Description
R/W
■
Attribute Retentive
Description
R/W
■
Attribute Retentive
Description
R
■
U.M.
Default
-
-
U.M.
Default
0.0
A
U.M.
Default
0.1
s
U.M.
Default
0.0
A